Permit Number: TC-COM-1125-02155
Parcel: 133231890

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1125-02155
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2025 Commercial Building Standard APPROVED APPROVED AS NOTED: Safety glazing will be field verified for compliance in hazardous locations. Plan indicates mechanical system (RTU) existing with no change to unit.
12/23/2025 Commercial Electrical Standard APPROVED
12/23/2025 Commercial Mechanical Standard APPROVED
12/23/2025 Commercial Plumbing Standard APPROVED
12/30/2025 Site Zoning Standard APPROVED
12/10/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/05/2025 Site Engineering Standard NOT REQUIRED
12/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2025 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1125-02155
ADDRESS/PARCEL: (7760 E SPEEDWAY BL TUCSON, AZ 85710)
COMMENTS:
1. Show the route of the building water supply along with the location of both the existing 2” water meter and the reduced pressure backflow preventer assembly. Provide the size of the backflow preventer as well. Reference: Section 107.2.1, IBC 2018.
12/26/2025 Fire New Construction Standard REVIEW COMPLETED
12/04/2025 PDSD Application Completeness Express REVIEW COMPLETED