Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2026 Commercial Electrical Standard APPROVED
02/02/2026 Commercial Plumbing Standard APPROVED
01/13/2026 Outdoor Lighting Standard APPROVED
02/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/02/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The use of an occupant load based on an engineering analysis requires an appeal to the building official: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/appeal_form4.pdf Show how the occupant load used in your calculation is supported for meeting room 1 and the multi-purpose room. Meeting room 2 could be described as conference room with an occupant load of 50 occupants per 1,000 square feet, or 12 occupants, instead of the 10 occupants you specify, without an appeal.
2. Ventilation for the apartment has not been addressed. Ventilation for R-2, R-3, or R-4 occupancies, thee stories or less require mechanical ventilation complying with Section 403.3.2, IMC 2018. Reference: Section R403.6, IECC 2018.

[Initial comment: Provide calculations to verify that adequate ventilation will be provided for all of the occupied spaces. Note: the occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation for the auditorium is to be based on Table 403.3.1.1, IMC 2018 or an approved (i.e., requires an appeal to the building official) engineering analysis of the specific occupancy type. Reference: Sections 401.2, 403.3.1.1, 403.3.1.1.2.3, and 403.3.2, IMC 2018.]