Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1125-02118
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 11/26/2025 | Site Engineering Standard | NOT REQUIRED | |||
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| N/A | Site Zoning Standard | PENDING ASSIGNMENT | |||
| 12/11/2025 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1125-02118 ADDRESS: (731 W 40TH ST TUCSON, AZ 85713) COMMENTS: 1. CODE REVIEW a. VB - Non Sprinklered i. This is an R-4 Occupancy Classification. ii. This facility will have 10 clients. iii. The above will require Fire Sprinkler per IBC 903.2.8.2 and Fire Sprinkler Classification Matrix by Tucson Fire/AHJ Chief Building Official. iv. Please correct. 2. FLOOR PLAN a. Lighted Exit sign with battery backup is not present on the floor plan. i. Please locate & label on your floor plan. b. Fire Extinguisher not present on the floor plan. i. Please locate & label on your floor plan. 3. SITE PLAN a. Submit a Site Plan locating and labeling the following: i. Show the location of the parking stalls & the handicap stalls being used by this facility. ii. On the Site Plan show/indicate the Accessible route from drop off location to the accessible entry door complying to IBC 106 & ANSI A117. iii. In an Emergency, show/locate the gathering area/dispersal area where it is safe from danger minimum 50 ft away from structure per IBC 310.5 and 1028.5. 4. An Operator's License must be applied for with the State, the absence of this license shall void this building permit. 5. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. |
||
| 12/03/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1125-02118 (731 W 40TH ST TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide a panel schedule highlighting the circuits that are being modified and added. Correlate the panel schedule circuit numbers with the location of the electrical outlets, receptacles, switches, mechanical equipment, etc, on the electrical plan. 2. Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4. 3. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, [NEC 210.52(D)]. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, [NEC 210.11(C)(3)] and [NEC 210.52(D)]. GFCI Protected, [NEC 210.8(A)]. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/15/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide specifications for the proposed exhaust fans. Reference: Section 403.3.1.1, IMC 2018. 2. Verify that the design for the termination of the clothes dryer exhaust to include a backdraft damper. Reference: Section 504.4, IMC 2018. 3. Show how the dryer installation complies with Section 504.6, IMC 2018. |
||
| 12/15/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. The International Plumbing Code, 2018, is the controlling code for this structure, not the International Residential Plumbing Code. Reference: Section 101.2, IPC 2018. 2. If the proposed shower will not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018. 3. Sizing pipes for water distribution systems using Appendix E, IPC 2018 is an accepted engineering method but Section E102.2.2 of Appendix E, IPC 2018 states that fixture units cannot be used for constant use items such as hose bibbs. A separate demand value for hose bibbs is to be added to the demand that was determined using fixture units. 4. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018. 5. Verify that the relocated washer box is equipped with water hammer arrestors that comply with ASSE 1010. Reference: Section 604.9, IPC 2018. 6. Clarify the routing and connections of the waste piping for the clothes washer and lavatory. Show the drainage fittings correctly installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. 7. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. |
||
| 12/15/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | Tucson Water limits a 5/8” meter to a maximum demand of 20 GPM. It appears that this address has a demand that exceeds 20 GPM but is served by a 5/8” water meter. Contact Tucson Water to have a ¾” water meter installed. | ||
| 11/24/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |