Permit Number: TC-COM-1124-02266
Parcel: 140420190

Address:
2701 E ELVIRA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1124-02266
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2024 Commercial Mechanical APPROVED
12/12/2024 Water - PDSD APPROVED
12/23/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/10/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the plans to include sheet D1.0, described in the Sheet Index as Demolition Plan, with the next submittal. IBC 107.2.1
2. Please provide structural calculations and construction drawings for the new door openings 10 feet in width. Currently, it appears the calculations only contain the calcs for only an opening of 8 feet in width. IBC 107.2.7
3. Please provide a note on the structural drawings to indicate the design is based on an evaluation of the existing construction, and only demolition will occur at the new openings. IBC 107.2.7
4. Please review the exit doors and where not accessible provide directional signage indicating the location of all other means of egress and which of those are an accessible means of egress shall be provided at.
A.At exits serving the required accessible space but not providing an approved accessible means of egress.
❖ The additional signage required by this section is intended to advise people of the locations of all means of egress and which of those also serve as accessible means of egress. Since not all of the exits will necessarily be an accessible means of egress, it is appropriate to provide this information regardless of whether they are part of an accessible means of egress. Directional signage is not required to meet raised character or braille signage requirements.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/09/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 REF; Plan sheets ‘E1.0’ and ‘E3.0’. The wording in the Schedules and notes are overlapped making them Un- legible. Please revise and resubmit the plans.

REf; 2018 IBC section 107.2.1.
12/12/2024 Commercial Plumbing REQUIRES RESUBMIT Revise Detail 208 to show access to the air admittance valve and a wall grille to allow air to enter the valve. Reference: Section 303.2, IPC 2018.
12/16/2024 Fire New Construction REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
12/20/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02266
2701 E ELVIRA RD

Site engineering comments are as follows:
1. The depiction of the loading docks, section detail “A” on the associated development package, TD-DEV-1124-00320, states that it is “Typical,” and no dimension for the width of the loading dock is given on this submission. Please provide a width dimension for the loading dock on the east side of the building.
2. Please provide drawdown calculations for the loading dock sump system. The drawdown time limits are 4 hours if the water is draining off-site, and 12 hours if it is remaining on-site. It is preferred that the dock discharge be routed to landscaped areas or water harvesting basins.
3. Since there is new construction outside of the building footprint, the associated development package, TD-DEV-1124-00320, must be approved by all reviewers prior to the approval of this permit submission. UDC Article 3.3.3.7.a

Ryan Insalaco – ryan.insalaco@tucsonaz.gov
12/23/2024 Site Zoning REQUIRES RESUBMIT FROM: Fernando Garcia - Planner PDSD Zoning Review Section
PROJECT:
Commercial Addition/Site Improvements
TC-COM-1124-02266 (Commercial Storage/General Manufacturing) (I-1) (1st Review)
2701 E Elvira Rd, Tucson, AZ 85756
TRANSMITTAL DATE: 12/23/2024
COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
01. COMMENT: Site Zoning has conducted a cursory review of the building permit plan set. Although the building permit appears to match the development package, Site Zoning cannot approve the building permit plan set until the development package has been reviewed and approved. Site Zoning will review the building plans on the next submittal and confirm compliance with the approved development package. For questions regarding Site Zoning comments, please contact me at fernando.garcia2@tucsonaz.gov.
12/05/2024 PDSD Application Completeness Express REVIEW COMPLETED