Permit Number: TC-COM-1124-02261
Parcel: 11603197B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02261
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2024 Commercial Mechanical APPROVED Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/10/2024 11:03:15 AM
12/10/2024 Commercial Plumbing APPROVED Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/10/2024 11:03:36 AM
01/06/2025 Site Zoning APPROVED
12/27/2024 Water - PDSD APPROVED
01/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/10/2024 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/10/2024 11:03:43 AM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 12/10/2024 11:00:51 AM
1. Sheet G0.0/Code Analysis: The code analysis states that panic hardware is not required. Based on the occupant load
calculations, panic hardware would be required. Provide panic hardware in accordance with 2018 IBC Section
1010.1.10.
2. Sheet G0.0/Code Analysis: The code analysis states that exit signage is not required. Based on the design provided exit signage would be required. Provide exit signage in accordance with 2018 IBC Section 1013.
3. Sheet G0.0/Code Analysis: It appears that no egress illumination has been provided. Provide egress illumination in accordance with 2018 IBC Section 1008.
4. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC). ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise
Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2)
12/10/2024 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 12/10/2024 11:03:05 AM
1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC) for any new Interior and Exterior Lighting.
◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2)
12/27/2024 Fire New Construction REQUIRES RESUBMIT -Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
12/05/2024 PDSD Application Completeness Express REVIEW COMPLETED
12/24/2024 Site Engineering REVIEW COMPLETED