Permit Number: TC-COM-1124-02243
Parcel: 11105030F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1124-02243
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2025 Water - PDSD APPROVED
01/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/13/2025 Commercial Electrical REQUIRES RESUBMIT January 2, 2025
1st Review

Seaver Franks Architects
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02243
Stantec Project Number: 185215066
Stantec File Number: TUC-24-151

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 7,747 346 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: Concrete, epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. Please include on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

Sheet S2.1

1. Please include concrete in the special inspections section as the concrete design strength indicates 3,000 psi. [Ref. IBC 2018 Sec. 1705.3]

Sheet S1.2

2. The Exhaust fan (EF-1) exceeds the design max weight limit of 475lbs indicated. Please revise.

MECHANICAL COMMENTS

Sheet M1.4

1. Plans including a commercial kitchen ventilation system shall include a schedule or diagram indicating the design outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

2. Please indicate duct smoke detector in the return air ducts of air distribution systems moving more than 2,000 cfm. [Ref. IMC 2018 Sec. 606.2.1]

Sheet M3.5

1. The exhaust fan (EF-1) weighs 551lbs but the structural engineer has designed for a maximum weight of 475lbs. Please revise.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2025 Commercial Mechanical REQUIRES RESUBMIT January 2, 2025
1st Review

Seaver Franks Architects
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02243
Stantec Project Number: 185215066
Stantec File Number: TUC-24-151

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 7,747 346 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: Concrete, epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. Please include on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

Sheet S2.1

1. Please include concrete in the special inspections section as the concrete design strength indicates 3,000 psi. [Ref. IBC 2018 Sec. 1705.3]

Sheet S1.2

2. The Exhaust fan (EF-1) exceeds the design max weight limit of 475lbs indicated. Please revise.

MECHANICAL COMMENTS

Sheet M1.4

1. Plans including a commercial kitchen ventilation system shall include a schedule or diagram indicating the design outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

2. Please indicate duct smoke detector in the return air ducts of air distribution systems moving more than 2,000 cfm. [Ref. IMC 2018 Sec. 606.2.1]

Sheet M3.5

1. The exhaust fan (EF-1) weighs 551lbs but the structural engineer has designed for a maximum weight of 475lbs. Please revise.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2025 Commercial Plumbing REQUIRES RESUBMIT January 2, 2025
1st Review

Seaver Franks Architects
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02243
Stantec Project Number: 185215066
Stantec File Number: TUC-24-151

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 7,747 346 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: Concrete, epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. Please include on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

Sheet S2.1

1. Please include concrete in the special inspections section as the concrete design strength indicates 3,000 psi. [Ref. IBC 2018 Sec. 1705.3]

Sheet S1.2

2. The Exhaust fan (EF-1) exceeds the design max weight limit of 475lbs indicated. Please revise.

MECHANICAL COMMENTS

Sheet M1.4

1. Plans including a commercial kitchen ventilation system shall include a schedule or diagram indicating the design outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

2. Please indicate duct smoke detector in the return air ducts of air distribution systems moving more than 2,000 cfm. [Ref. IMC 2018 Sec. 606.2.1]

Sheet M3.5

1. The exhaust fan (EF-1) weighs 551lbs but the structural engineer has designed for a maximum weight of 475lbs. Please revise.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2025 Commercial Structural REQUIRES RESUBMIT January 2, 2025
1st Review

Seaver Franks Architects
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1124-02243
Stantec Project Number: 185215066
Stantec File Number: TUC-24-151

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 V-B 7,747 346 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: None.
Special Inspections: Concrete, epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. Please include on the cover of the drawings that special inspection is required for concrete. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

Sheet S2.1

1. Please include concrete in the special inspections section as the concrete design strength indicates 3,000 psi. [Ref. IBC 2018 Sec. 1705.3]

Sheet S1.2

2. The Exhaust fan (EF-1) exceeds the design max weight limit of 475lbs indicated. Please revise.

MECHANICAL COMMENTS

Sheet M1.4

1. Plans including a commercial kitchen ventilation system shall include a schedule or diagram indicating the design outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

2. Please indicate duct smoke detector in the return air ducts of air distribution systems moving more than 2,000 cfm. [Ref. IMC 2018 Sec. 606.2.1]

Sheet M3.5

1. The exhaust fan (EF-1) weighs 551lbs but the structural engineer has designed for a maximum weight of 475lbs. Please revise.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/02/2025 Fire New Construction REQUIRES RESUBMIT -Make a note that a fire alarm will be installed per IFC 907.2.1 and NFPA 72. A fire alarm is required per this section due to the OL being over 299.
-Please provide more information on your multipurpose hall. Will there be dividers that separate the spaces? This information is needed to determine the number of exits required for each space if dividers are used.
john.vincent@tucsonaz.gov
5203495581
01/07/2025 Site Engineering REQUIRES RESUBMIT 1. A floodplain use permit is required and must be issued before this building permit can be approved. Please provide a PDF cost estimate for materials and labor for the floodplain use permit, and please also resubmit for this building permit.

Mike Ortiz
michael.ortiz@tucsonaz.gov
01/10/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1124-02243 - TD-DEV-0523-00234
3201 E PRESIDIO RD BLDG 4. – R-2
Religious Use: Kitchen Addition (1st Review)

TRANSMITTAL DATE: January 10, 2025

Resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). Religious Use is a permitted use in this zone (Table 4.8-2).

1. Zoning has reviewed the TI for compliance with Development Package (DP) TD-DEV-0523-00234, and all though the plans appear to match until the DP is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/13/2024 PDSD Application Completeness Express REVIEW COMPLETED