Permit Number: TC-COM-1124-02200
Parcel: 12416001A

Address:
602 E 24TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02200
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2024 Commercial Structural APPROVED
12/10/2024 Site Zoning APPROVED
11/26/2024 Water - PDSD APPROVED
12/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/02/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide power for the electrical Heat Pump in the power plan and correlate with the associated panel schedule. See Mechanical plans for specifications.

2 Provide power and controls for the restroom exhaust fans. See Mechanical plans for specifications.

3 The electrical system for this project exceeds 400 amp. Per City of Tucson policy, please provide all electrical design and calculations (Including total electrical service load calculations), plans sealed by an Electrical Engineer registered in the State of Arizona.

3a. Provide a complete electrical line diagram showing all downstream electrical equipment, including Breaker Panels, Transformers, and AIC ratings, also show what is new and what is existing.

3b. Provide a complete grounding detail. Include grounding for the transformer.

3c. Provide disconnecting means for the transformer secondary feeder or if within 25’ of Panel ‘LV’, verify that Panel ‘LV’ is equipped with a main circuit breaker for protection. NEC art’s 408.36(b) and 450.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Review Requirements.
11/26/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Ventilation for copy/print rooms requires mechanical exhaust of at least 0.5 CFM per square foot. Reference: Section 403.3.1.1, IMC 2018 and Table 403.3.1.1, IMC 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
11/26/2024 Commercial Plumbing REQUIRES RESUBMIT Provide a site drawing showing the route, and slope of the 4” building sewer (see Keynote 1, P1.0) and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2018.
11/29/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02200
602 E 24TH ST

Site engineering comments are as follows:
1. This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home
NOTE: A cost estimate of materials and labor from your contractor in the form of a pdf attachment will be required to complete the FUP application. Please have separate lines for cost of materials, and cost of labor. Thank you.
Ryan Insalaco
Email: ryan.insalaco@tucsonaz.gov
12/02/2024 Fire New Construction REVIEW COMPLETED
11/15/2024 PDSD Application Completeness Express REVIEW COMPLETED