Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1124-02192
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/09/2024 | Site Zoning | APPROVED | |||
12/10/2024 | Water - PDSD | APPROVED | |||
11/29/2024 | Site Engineering | NOT REQUIRED | |||
12/10/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/27/2024 | Commercial Building | REQUIRES RESUBMIT | Sheet 1 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM) 1. Sheet 1 Provide code analysis for building to include construction type, occupancy types, occupant load, sprinklers, alarms, exiting requirements for distance and sizes, and minimum plumbing requirements. Incomplete 2018 IBC 107.2.1 (BM) 2. Sheet #2 Provide for review, existing floor plan to compare with new floor plan. Also identify demo areas on existing plan. Provide new floor plan with dimensions of all rooms and areas. Incomplete 2018 IBC107.2.1 (BM) 3. Sheet #2 Provide a door schedule to include all door types, sizes and hardware to comply with 2018 IBC 1010.1.1 & ICC A117 (BM) [ Ver. 2 ] [Edited By Bill McClellan] 4. Sheet #2 Provide on plans all ADA dimensions for counters, reception counter and restroom clearances and approach. Incomplete ICC A117 & 2018 IBC 107.2.1 (BM) 5. Sheet #2 Keynotes #10 & #14 identifies larger door openings in bearing wall. Provide framing detail identifying proposed header and support framing for opening. Incomplete 2018 IBC 107.2.1 (BM) 6. Sheet #3 MEP Keynotes #1 identifies to remove existing ceiling. Clarify new ceiling type and design for area to comply with building construction, insulation and thermal envelope. Incomplete 2018 IBC 107.2.1 (BM) [ Ver. 2 ] [Edited By Bill McClellan] |
||
11/27/2024 | Commercial Electrical | REQUIRES RESUBMIT | 1. Sheet #3 With all fixtures noted to be replaced, provide a light fixture schedule to include all fixtures to include EM and exit signs. 2018 IBC 107.2.1 Will need to provide an interior lighting compliance certificate to comply with 2018 IECC C405 (BM) 2. Sheet #3 Provide for review, electrical plan to identify existing receptacles, lights, and switches along with new / relocated electrical receptacles and lighting added to floor plan. Incomplete 2018 IBC 107.2.1 (BM) [ Ver. 2 ] [Edited By Bill McClellan] |
||
11/27/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Sheet #3 Provide for review, mechanical plan to include typical notes, duct sizes, support and register sizes with CFM. Incomplete 2018 IBC 107.2.1 (BM) [ Ver. 2 ] [Edited By Bill McClellan] |
||
11/27/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Sheet #2 Provide dimensions and details for new ADA restroom to comply with ICC A117 requirements. Incomplete 2018 IBC 107.2.1 (BM) 2. Sheet #3 Provide for review, plumbing plan to include typical notes for domestic water, DWV and fixture types for added, removed and relocated fixtures. Incomplete 2018 IBC 107.2.1 (BM) [ Ver. 2 ] [Edited By Bill McClellan] |
||
11/29/2024 | Fire New Construction | REQUIRES RESUBMIT | -Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
11/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |