Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02191
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2024 Commercial Electrical APPROVED
12/02/2024 Commercial Plumbing APPROVED
12/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/16/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Sheet G1.001 Provide a letter to Building Official to verify that keeping the doors open will satisfy the code requirement for mechanical ventilation.
12/02/2024 Commercial Structural REQUIRES RESUBMIT Ed Kulik ekulik@willdan.com
1. Sheet G1.001 Provide roof truss layout and calculations.
2. Sheet A1.101 Show the ADA POS area. Provide details of check out counter.
3. Structural Calculations Verify the Rigid diaphragms.
11/29/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02191
3925 E 22nd ST

The building permit cannot be approved until the associated development package, TD-DEV-0723-00310, has been approved.

Chris Arrington
chris.arrington@tucsonaz.gov
12/09/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-1124-02191 - TD-DEV-0723-00310
3925 E 22ND ST. - C-2
Automotive: Minor Service and Repair ( Review)

TRANSMITTAL DATE: ‎July 22, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Automotive: Minor Service and Repair is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E.

1. Zoning has reviewed this building plan for compliance with Development Package (DP) TD-DEV-0723-00310 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/02/2024 Water - PDSD REQUIRES RESUBMIT 1. Sheet G1.001 Provide a letter to Building Official to verify that keeping the doors open will satisfy the code requirement for mechanical ventilation.
11/29/2024 Fire New Construction REVIEW COMPLETED
11/14/2024 PDSD Application Completeness Express REVIEW COMPLETED