Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1124-02191
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2024 | Commercial Electrical | APPROVED | |||
| 12/02/2024 | Commercial Plumbing | APPROVED | |||
| 12/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/16/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Sheet G1.001 Provide a letter to Building Official to verify that keeping the doors open will satisfy the code requirement for mechanical ventilation. | ||
| 12/02/2024 | Commercial Structural | REQUIRES RESUBMIT | Ed Kulik ekulik@willdan.com 1. Sheet G1.001 Provide roof truss layout and calculations. 2. Sheet A1.101 Show the ADA POS area. Provide details of check out counter. 3. Structural Calculations Verify the Rigid diaphragms. |
||
| 11/29/2024 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1124-02191 3925 E 22nd ST The building permit cannot be approved until the associated development package, TD-DEV-0723-00310, has been approved. Chris Arrington chris.arrington@tucsonaz.gov |
||
| 12/09/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-1124-02191 - TD-DEV-0723-00310 3925 E 22ND ST. - C-2 Automotive: Minor Service and Repair ( Review) TRANSMITTAL DATE: ‎July 22, 2024 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Automotive: Minor Service and Repair is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E. 1. Zoning has reviewed this building plan for compliance with Development Package (DP) TD-DEV-0723-00310 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 12/02/2024 | Water - PDSD | REQUIRES RESUBMIT | 1. Sheet G1.001 Provide a letter to Building Official to verify that keeping the doors open will satisfy the code requirement for mechanical ventilation. | ||
| 11/29/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 11/14/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |