Permit Number: TC-COM-1124-02168
Parcel: 14041009A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1124-02168
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2025 Site Engineering APPROVED
02/03/2025 Site Zoning APPROVED
02/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/21/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/13/2025 3:47:28 PM



Building(B) Reviewer (from previous submittal TUC9626001.111324)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/25/2024 4:41:15 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 1/14/2025 1:17:05 PM
1. General - Provide Heat Load Calculations. Show all ventilation Cooling and Heating loads. - 2018 IECC Section
C403.1.1 Calculation of heating and cooling loads.
i. Heat Loads are not Energy loads. Provide Heat Load Calculations. Include all Ventilation loads in the
calculations. only APPROVED calculation programs are acceptable. As per the stated 2018 IECC noted:
▪ Design loads associated with heating, ventilating and air conditioning of the building shall be determined
in accordance with ANSI/ASHRAE/ACCA Standard 183 or by an approved (approved by the Authority
Having Jurisdiction) equivalent computational procedure using the design parameters specified
in Chapter 3. Heating and cooling loads shall be adjusted to account for load reductions that are
achieved where energy recovery systems are utilized in the HVAC system in accordance with
the ASHRAE HVAC Systems and Equipment Handbook by an approved equivalent computational
procedure. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.




Electrical(E) Reviewer (from previous submittal TUC9626001.111324)
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 11/25/2024 10:30:44 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/18/2025 9:23:29 AM
Second Plumbing Review: OK SUBJECT TO FIELD INSPECTIONS
RESOLVED-1). Plan Page A1.2: Missing Gutter & downspout sizing calculations. Add Gutter & downspout sizing calculations.-2018 IPC 1106.3, 1106.6
RESOLVED-2). General: Missing route illustrations and distance to restrooms & High/Low drinking fountain that services this Building. Add the route illustrations and distance to restrooms & High/Low drinking fountain that services this Building.-2018
IPC 403.3.1, 403.3.3, 403.5
RESOLVED-3). General: Plans missing fixture count totals for all correlated spaces. Add fixture count totals for all correlated spaces. -2018 IPC 403.1
RESOLVED-4). Plan Pages M5.3 & M6.1: Lift station Details missing shut off valve & check Valve. Add shut off valve & check Valve to lift station Detail. -2018 IPC 712.2
RESOLVED-5). Mechanical Plans: Missing Acid Neutralizing device detail & location. Add Acid Neutralizing device detail & location. -IPC 2018 803.1, 803.2 **EXISING NEUTRALIZING DEVICE TO REMAIN AS STATED IN RESPONSE
COMMENTS-SUBJECT TO FIELD INSPECTIONS**
RESOLVED-6). Plan Page M2.3: Hose bib missing Shut off valve. Add Shut off valve on hose bib piping. -2018 IPC 606.2
01/13/2025 PDSD Application Completeness Express REVIEW COMPLETED