Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
3350 E VALENCIA RD
Apply Date:
11/12/2024
Applicant:
Bryce Davis
Description:
Open Lab Area (Warehouse)

Permit Reviews

Permit Number - TC-COM-1124-02168
Permit Status: Issued
Permit Description: Open Lab Area (Warehouse)
Start Date Submittal Complete Date Status  
02/11/2025 RESTAMP - COMMERCIAL v.1 02/13/2025 APPROVED Review Details
01/13/2025 COMMERCIAL REVIEW - FULL v.2 02/04/2025 REQUIRES RESUBMIT Review Details
04/16/2026 COMMERCIAL REVIEW - FULL REVISION v.2 04/23/2026 APPROVED Review Details
04/02/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.2 04/07/2025 APPROVED Review Details
02/20/2026 COMMERCIAL REVIEW - FULL REVISION v.1 03/16/2026 REQUIRES RESUBMIT Review Details
02/11/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.2 02/12/2026 REQUIRES RESUBMIT Review Details
03/28/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 04/02/2025 REQUIRES RESUBMIT Review Details
05/06/2026 SPECIAL INSPECTION REVIEW v.1 N/A IN REVIEW Review Details
02/08/2025 COMMERCIAL REVIEW - FULL v.3 02/08/2025 REQUIRES RESUBMIT Review Details
11/13/2024 COMMERCIAL REVIEW - FULL v.1 12/10/2024 REQUIRES RESUBMIT Review Details
12/19/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/22/2025 REQUIRES RESUBMIT Review Details
02/10/2025 COMMERCIAL REVIEW - FULL v.4 02/11/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1124-02168
Permit Status: Issued
Permit Description: Open Lab Area (Warehouse)
Total Outstanding Activity Conditions - 7
Date Name
02/11/2025 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
02/11/2025 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
02/11/2025 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
02/11/2025 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
02/11/2025 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
02/11/2025 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
04/21/2026 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.

Conditions

Permit Number - TC-COM-1124-02168
Permit Status: Issued
Permit Description: Open Lab Area (Warehouse)
Date Description Comments
11/13/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
02/08/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
02/11/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-1124-02168
Permite Description: Open Lab Area (Warehouse)
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
06/11/2026 COT - HCBU - Framing N/A Partial Pass 6-11-26: partial pass-pending racking system installation.
06/15/2026 COT - HCME - Mechanical Intermediate N/A Canceled 6-15-26: canceled by contractor.
06/15/2026 COT - HCME - Mechanical Progress N/A Canceled 6-15-26: canceled by contractor.
10/02/2025 COT - HCPL - Plumbing Progress N/A Partial Pass 10-2-25: referred contractor to engineering department supervisor for storm drain questions/inspections.
07/23/2026 COT - HCPL - Plumbing Intermediate N/A Partial Pass 7-23-26: pending pressure test at DWV/Copper lines.
10/28/2025 COT - HCEL - Electrical Progress N/A Partial Pass
07/23/2026 COT - LCEL - Outdoor Lighting N/A Partial Pass 7-23-26: pending 3rd party report to the city for review & approval. Exterior receptacle covers must be rated "heavy duty-while in use."
07/23/2026 COT - BULD - SWG Clearance N/A Not Applicable 7-23-26: not applicable.
07/23/2026 BULD - Electrical Clearance N/A Not Applicable 7-23-26: not applicable.
08/10/2026 COT - HCBU - Building Final N/A Canceled
08/10/2026 COT - HCME - Mechanical Final N/A Canceled

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-1124-02168
Permit Description: Open Lab Area (Warehouse)
Total Completed Inspections - 11
Date Description Inspector Results Comments
06/11/2026 COT - HCBU - Exterior Clips/Sheathing Passed 6-11-26: exterior clips/sheathing approved.
06/11/2026 COT - HCBU - Building Progress Passed 6-11-26: exterior clips/sheathing approved.
06/11/2026 COT - HCBU - Roof Nailing Passed 6-11-26: roof nailing approved.
07/23/2026 COT - HCPL - Plumbing Progress Passed 7-23-26: plumbing progress approved.
07/23/2026 COT - HCPL - Plumbing Above Ceiling Passed 7-23-26: plumbing above ceiling approved.
07/23/2026 COT - HCME - Mechanical Above Ceiling Passed 7-23-26: mechanical above ceiling approved.
07/23/2026 COT - HCEL - Electrical Progress Passed 7-23-26: electrical progress approved.
07/23/2026 COT - HCEL - Electrical Intermediate Passed 7-23-26: electrical intermediate approved.
07/23/2026 COT - HCEL - Electrical Above Ceiling Passed 7-23-26: electrical above ceiling approved.
08/10/2026 COT - HCBU - Building Above Ceiling Passed Passed
08/10/2026 COT - HCPL - Plumbing Final Passed Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
2-9-26-FMI-TCT-REV 1_V1.PDF DOCUMENTS VIEW
42201.00 - ELEC SITE LIGHTING CITY COMMENTS - DRAWINGS 26-0410_V1.PDF DOCUMENTS VIEW
NARRATIVE OF CHANGE_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-42201.00 AHJ RESPONSE COMPOSITE DRAWINGS_V3.PDF DOCUMENTS VIEW
122421 FREEPORT TUCSON 42201.00 STRUCTURAL CALCULATIONS_V2.PDF DOCUMENTS VIEW
22-125 FREEPORT TECHNOLOGY CENTER GEOTECHNICAL REPORT_V2.PDF DOCUMENTS VIEW
COMCHECK-42201.00 FMI-TCT TUCSON-SIGNED_V2.PDF DOCUMENTS VIEW
TRANE TRACE OUTPUTS 25-0206_V2.PDF DOCUMENTS VIEW