Permit Number: TC-COM-1124-02162
Parcel: 140420190

Address:
2721 E ELVIRA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1124-02162
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2024 Water - PDSD APPROVED
12/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/26/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 11/26/2024 3:55:47 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be
reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.
2. S2.0 - NEW OPENINGS IN EXISTING CONCRETE WALL: The Structural Composite Plan, S2.0, indicates five locations where new openings shall be installed in the existing exterior concrete walls. The structural calculations indicate that new openings shall be a maximum of 8'-0" wide and assume that the existing concrete walls are at least 6" thick, with reinforcement equivalent to #4 horizontal bars @ 12" oc and two #3 vertical bars at 11" oc. Please provide a note on the structural drawings to indicate how these existing conditions shall be confirmed prior to installing new openings and amend the Structural Details 101, 102, 103 or 104 to indicate that openings shall not exceed 8'-0" in width.
3. S2.0 - RAMP SLAB: Per the Structural Composite Plan S2.0, Plan Note 10, the new concrete ramp slab shall be designed by the civil engineer, and therefore is not structural. However, the structural calculations for retaining walls DRW1 thru DRW4 indicate that the walls shall be reinforced against sliding by the adjacent concrete slab. If the slab is being relied upon for the stability of the ramp retaining walls, the structural engineer must provide a minimum concrete thickness and reinforcement. Please provide this information or resubmit the calculations to show the walls are
capable of retaining soil without contributions from the slab.
4. STRUCTURAL CALCULATIONS - RETAINING WALLS: The structural general notes indicate that there has been no site-specific geotechnical study conducted for this project. Therefore, the foundation modifications have been designed using the Presumptive Soil Load Bearing values provided in the 2018 IBC Table 1806.2 (1,500 psf for soil types CL, ML, MH or CH). Similarly, for design of retaining walls, in the absence of a geotechnical study, the engineer
is required to use the lateral soil loads provide in IBC Table 1610.1. Refer to IBC 1807.1.1 for more information. For soil types CL or ML, the minimum active soil pressure shall be 45 psf or 60 psf, and the maximum passive pressure
shall be 100 psf. Please revise the provided structural calculations to confirm the retaining wall designs are sufficient under these revised forces.





Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/25/2024 9:50:38 AM





Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 11/22/2024 10:10:41 AM
1. General - Provide Existing Unit Schedule. Provide all required information. Confirm Total CFM quantities for Supply Air Drops for each specific existing unit. Match Unit schedule amounts for each specific existing system. - 2018 IECC
Section C103.2Information on construction documents - 2018 IBC – Section [A]107.2.1Information on construction documents.
2. Plan Sheet M1.0 - Supply Air branches with Supply grill/diffuser not shown on plans . Show all Supply air branches and Supply grills/diffusers. - 2018 IECC Section C103.2Information on construction documents - 2018 IBC – Section
[A]107.2.1Information on construction documents.
3. Plan Sheets M0.0 and M1.0 - Existing unit AC3 shows main supply trunk line labeled as a RA duct. Confirm main supply air duct Tag. - 2018 IECC Section C103.2Information on construction documents - 2018 IBC – Section [A]107.2.1Information on construction documents





Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 11/23/2024 5:34:29 PM







Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/17/2024 1:58:57 PM
First Plumbing Review:
1). General: This occupancy type & load requires a High/low drinking fountain & service sink. Add the required plumbing fixtures, illustrations & information to all the affected plan pages. -2018 IPC 403.1 (plumbing page P0.0 show drinking
fountain & service sink being demoed the new one do not appear on new building & plumbing floor plan pages)
11/29/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1124-02162
2721 E ELVIRA RD

Site engineering comments are as follows:
1. The site plan (TD-DEV-1124-00320) must be approved by all reviewers prior to approval of this building permit. UDC Article 3.3.3.7.a
2. Please provide oil filtration on all loading dock sump pumps to prevent pollutant discharge into storm water infrastructure.
Ryan Insalaco
ryan.insalaco@tucsonaz.gov
12/06/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1124-02162 - TD-DEV-1124-00320
2721 E ELVIRA RD. – I-1
Commercial Storage (1st Review)

TRANSMITTAL DATE: December 6, 2024

Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 zone (UDC 4.7.29). Commercial Storage is an allowed use in the zone (UDC Table 4.8-7), subject to a Use Specific Standards 4.9.10.A and 4.9.13.Q.

1. As Development Package (DP) TD-DEV-1124-00320 has not completed its first review Zoning cannot review the building plans for compliance with the DP and will review on the next submittal. Until the DP is approved by all review agencies Zoning cannot approve this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/26/2024 Fire New Construction REVIEW COMPLETED
11/12/2024 PDSD Application Completeness Express REVIEW COMPLETED