Permit Number: TC-COM-1124-02121
Parcel: 140420120

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1124-02121
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2024 Commercial Building APPROVED
12/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/19/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 This project includes areas categorized as Hazardous areas per 2017 NEC arts 514 and 515. Please provide electrical power and lighting plans with calculations and design, sealed by an Electrical Engineer registered in the State of Arizona.

2 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for any exterior lighting modifications.

REF; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
11/20/2024 Site Engineering REQUIRES RESUBMIT 1. A development package is required for this project and must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
12/02/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1124-02121
1961 E AIRPORT DR. BLDG 1 – MU
Expansion of the fuel island - TIA ( 1st Review)

TRANSMITTAL: December 2, 2024
This site is located in the MU zone (4.7.23). Transportation Service: Airport Authority is an allowed use in the zone (UDC Table 4.8-7), subject to Use Specific Standard 4.9.13.Q.5.

1. The development package sheets provided in the building plan set either need to be the stamped approved plans, marked for reference only, or removed from the building set. This DP will need to be approved prior to approve of the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/17/2024 Fire New Construction REVIEW COMPLETED Contact Inspector Jesus Silva for fire inspections:
jesus.silva@tucsonaz.gov
5208377094
5204199177
11/05/2024 PDSD Application Completeness Express REVIEW COMPLETED