Permit Number: TC-COM-1123-02689
Parcel: 136048100

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1123-02689
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2024 7:24:54 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 7/15/2024 11:43:03 AM





Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 12/1/2023 2:54:11 PM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/14/2024 10:00:07 PM
Second plumbing review: Ok
08/14/2024 Water - PDSD APPROVED
08/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/08/2024 Fire New Construction REQUIRES RESUBMIT -Please provide an explanation of occupancy type classification of B (business), Cover sheet (code review checklist). It appears it should either be an A3 or mixed use A3/B.
john.vincent@tucsonaz.gov
5203495581
08/13/2024 Site Engineering REQUIRES RESUBMIT 1. It is not clear whether the roof gutter system is proposed to connect to the sanitary sewer system. This is not allowed. Additionally, the location of the downspout is in close proximity to the ADA parking space. Stormwater from roof drains may not pass over ADA sidewalks per TSM 7-01.4.3E. Please propose the roof downspout in a different location away from the ADA parking space, ensure it is not to be connected to the sewer system, and use a scupper under the sidewalk, if applicable.

Mike Ortiz
michael.ortiz@tucsonaz.gov
08/08/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1123-02689
8815 E GOLF LINKS RD – C-1
Commercial Recreation - Gymnasium (2nd Review)

TRANSMITTAL: August 8, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food Service: Excluding Soup Kitchens is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.O.

1. This comment was not addressed. Zoning has reviewed the building plans for compliance with Development Package (DP) DP18-0082, but it does not appear that the plans match. This building plan shows a square footage of 6,372 (LOWER LEVEL + MEZ) and an 180 SF Patio but the DP only shows 5,400 SF and does not reference a mezzanine or patio. Either the building plans will need to be changed to match the DP or a revision to the DP is required.

2. Sheet SP1 does not match the approve DP submitted with this plan. The 3 parking space shown north of the proposed building still show as a dumpster location on the DP. One of the plans will need to be modified so that the plans match.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/12/2024 PDSD Application Completeness REVIEW COMPLETED