Permit Number: TC-COM-1123-02607
Parcel: 10602001C

Address:
3954 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1123-02607
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2023 Site Zoning APPROVED
12/05/2023 Water - PDSD APPROVED
12/12/2023 Site Engineering NOT REQUIRED
12/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/16/2023 3:48:01 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/16/2023 3:46:37 PM
1) Sheet G002: Include the actual building height to the project and code information. (2018 IBC Chapter 5)

2) Sheet G002: Show the uses of the adjacent spaces to determine the fire-rated separation as required in 2018 IBC Table 508.4.

3) Sheet G002: The waiting area is an assembly use for seating only and is to be calculated at 1 person per 7 sf. The break room is to be calculated at 1 person per 15 sf for table and chairs. Please revise the occupant load and minimum plumbing
fixture calculations and all affected sheets. (2018 IBC Table 1004.5)

4) Sheet E1.0: Receptacles less than 6ft to sinks are to be GFCI protected. Please identify all GFCI protected receptacles. (2017 NEC section 210.8(B)(5)

5) Sheet E1.0: Missing rooftop GFCI protected receptacles for the HVAC equipment service. (2017 NEC section 210.63)

6) Sheet E1.0: Specify tamper-resistant receptacles as required by 2017 NEC section 406.12.



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/16/2023 3:47:22 PM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/16/2023 3:47:06 PM
See the building review comments



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/16/2023 3:47:45 PM
See the building review comments
11/13/2023 Fire New Construction REVIEW COMPLETED
11/09/2023 PDSD Application Completeness REVIEW COMPLETED