Permit Number: TC-COM-1122-00184
Parcel: 14042065C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1122-00184
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: TC-COM-1122-00184

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
APPROVED
Approved with the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
E2.1 ELECTRICAL LIGHTING PLAN - NORTH: Keynotes 4 & 5 are identical.
E2.2 ELECTRICAL LIGHTING PLAN - SOUTH: Keynote 4 was not near any fixture H.
E3.7 ELECTRICAL SECURITY PLAN - SOUTH: Could not located Keynotes 1 and 2.
E4.1 ELECTRICAL ENLARGED PLANS LIGHTING: Could not located Keynote 2.
E5.1 ELECTRICAL SINGLE LINE DIAGRAM PHASE 1:
Could not locate a 225S feeder (Panel feeds for LPD and LPF) in Feeder schedules.
Comment only, Feeders to panel HPF are oversized.
E5.2 ELECTRICAL SINGLE LINE DIAGRAM PHASE 2:
Could not locate a 225S feeder (Panel feeds for LPD and LPF) in Feeder schedules.
Comment only, Feeders to panel HPF are oversized.
Wrong Keyed Note # next to Generator.
Wrong or should be deleted Keyed Note #1 next to transformer ground.


PLUMBING REVIEW COMMENTS:
CONDITIONALLY APPROVED
Second Plumbing Review: OK subject to Field Inspections
1) OK
2). OK, connect sand/oil interceptor on plan page C1.1 to Vent #6 shown on plan page P2.0 ** Subject to Field Inspections
3). OK
4). OK
5). OK
6). OK Gas Unit heater combustion air method Subject to Field Inspections & manufacturer specs


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/10/2023 PDSD Application Completeness APPROVED
04/07/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/31/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-COM-1122-00184
6818 S Country Club Rd – I-1
TI Commercial Storage (1st Review)

TRANSMITTAL: December 08, 2022

This site is located in the I-1 zone (UDC 4.9.29). A Commercial Storage is a permitted use in this zone (Table 4.8-5), subject to Use Specific Standards 4.9.10.A and 4.9.13.Q.

Until the revision to DP20-0173 is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.