Permit Number: TC-COM-1122-00184
Parcel: 14042065C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1122-00184
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/30/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00184

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED1. Provide Structural Calculations for Mezzanine and Ceiling Framing per Section 1601.1 of International Building Code 2018.
2. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
4. Provide Material Structural Notes for all materials used in this project.
5. Refer to Structural Drawing S1.3, Detail B/S1.3 shows new units supported on existing 30K Joists. Verify adequacy of these Joists to carry additional loading from New Units.
6. Refer to Structural Drawing S2.1 showing New Stairs supported on existing Slab. Verify adequacy of the existing slab to support the new loadings from the new stairs.
7. Refer to Structural Drawing S2.1 showing New HVAC unit weighing 800#s supported on existing Steel Joists. Verify the adequacy of existing Roof System to support the additional loading.


Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
DENIED
1. Cover Sheet / Building Statistics / Occupancy: Revise to indicate if the mixed occupancies are “separated mixed occupancies” or “non-separated mixed occupancies”. If separated mixed occupancies, please indicate the rated separations per 2018 IBC Table 508.4. (2018 IBC Sec. 508.1, 508.4, & 508.5)
2. Cover Sheet / Building Statistics / Occupancy: Revise to indicate all Accessory Occupancies, per 2018 IBC Sec. 508.2.
3. Cover Sheet / Building Statistics / Occupancy: Revise to indicate all Incidental Uses and their method of protection, per 2018 IBC Sec. 509.1, 509.4, and Table 509.
4. Sheet A0.0 (Code Review Plan) / Building Code Summary (Table): Revise to indicate all Accessory Occupancies, per 2018 IBC Sec. 508.2.
5. Sheet A0.0 (Code Review Plan) / Building Code Summary (Table): Revise to indicate all Incidental Uses and their method of protection, per 2018 IBC Sec. 509.1, 509.4, and Table 509.
6. Sheet A0.0 (Code Review Plan) / IBC Code Review (Table): Revise to indicate the Common Path of Egress Travel Distance (2018 IBC Sec. 1006.2.1 & Table 1006.2.1) and the Exit Access Travel Distance (2018 IBC Sec. 1017.2 & Table 1017.2).
7. Sheet A0.0 (Code Review Plan) / A/A0.00 (Overall Floor Plan): Revise the Life Safety Plan to include a dimensioned line indicating the path of egress travel from the most remote space to the point of exit discharge. (2018 IBC Sec. 1017.3) This line must also show the travel path around fixed / moveable objects and the divergence in the egress path at the point of the Common Path of Egress Travel. This point of divergence occurs at the point where the occupant can change directions to another exit discharge point within the total Exit Access Travel Distance. (2018 IBC Sec. 1017.2)
8. Sheet A4.0 (Stair Plan, Sections, and Details) / General: Revise the stair details to provide the visually contrasting stripe at the tread nosing, per ICC/ANSI A117.1-2009 Sec. 504.5.1.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
E2.1 ELECTRICAL LIGHTING PLAN - NORTH: Keynotes 4 & 5 are identical.
E2.2 ELECTRICAL LIGHTING PLAN - SOUTH: Keynote 4 was not near any fixture H.
E3.7 ELECTRICAL SECURITY PLAN - SOUTH: Could not located Keynotes 1 and 2.
E4.1 ELECTRICAL ENLARGED PLANS LIGHTING: Could not located Keynote 2.
E5.1 ELECTRICAL SINGLE LINE DIAGRAM PHASE 1:
Could not locate a 225S feeder (Panel feeds for LPD and LPF) in Feeder schedules.
Comment only, Feeders to panel HPF are oversized.
E5.2 ELECTRICAL SINGLE LINE DIAGRAM PHASE 2:
Could not locate a 225S feeder (Panel feeds for LPD and LPF) in Feeder schedules.
Comment only, Feeders to panel HPF are oversized.
Wrong Keyed Note # next to Generator.
Wrong or should be deleted Keyed Note #1 next to transformer ground.


PLUMBING REVIEW COMMENTS:
DENIED
First Plumbing Review:
1) Detail #3 on Plan page P4.7 needs the correct correlating Keynote numbers. -IPC 106.3.1
2). Add the required Sand/Oil waste interceptor illustrations to vehicle repair area plan page P4.3-IPC1003.4
3). Add lavatory mixing valve information to plan page P6.1 -IPC 419.5
4). Add the Sand/oil interceptor manufacture & model number information to plan page P6.1 along with sizing calculations. - IPC 1003.4.2
5). Hose reel water connection detail #4 on plan page D3.1 needs vacuum breaker.
6). Add Gas Unit heater combustion air method to plumbing or mechanical plans -IFGC 304


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/12/2023 Site Zoning REQUIRES RESUBMIT ShapeShape FROM: PDSD Zoning Review PROJECT: TC-COM-1122-00184 6818 S Country Club Rd – I-1 TI Commercial Storage (1st Review) TRANSMITTAL: December 08, 2022 This site is located in the I-1 zone (UDC 4.9.29). A Commercial Storage is a permitted use in this zone (Table 4.8-5), subject to Use Specific Standards 4.9.10.A and 4.9.13.Q. Sheet A1.1 shows a proposed mezzanine which was not accounted for on Development Package DP20-0173. A revision to the DP will need to be submitted and approved prior to approval of this plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.