Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00166
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/10/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00166

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.


BUILDING REVIEW COMMENTS:
APPROVED


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
E-702 ELECTRICAL SCHEDULES: Circuit breaker for sub panel F needs to be 60 amp to agree sheet E-601. If it stays at 150 Amp the EOR will need to be revise and resubmit E-601.


PLUMBING REVIEW COMMENTS:
DENIED
First Plumbing Review:
1). Clothes washer box in Decon room #126 on plan page PL 130 will need to connect to a 3" Bldg. drain -IPC 406.2
2). All clothes washers on plan page PL 130 will need to discharge to a lint interceptor regardless of type. -IPC 1003.6
3)., One of the 2 ice machines on plan page PP101 can't be located in the Decon room. -IPC 801.2
4). Keynote #2 on PL130 not illustrated on plan? -IPC 106.3.1



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/30/2022 Fire New Construction REQUIRES RESUBMIT -Cover sheet indicates fire sprinklers and fire alarm will be deferred submittals. Make appropriate corrections to this depending on fire protection requirements.
-Sheet FA101 shows fire alarm devices being added to an existing system. My records do not indicate there is a fire alarm at this location. Verify if the existing building has a fire alarm and make appropriate changes.
-Incorrect address on title block for many of the sheets. Electrical, mechanical, plumbing, FA. Make corrections.
-Code data/analysis lists IEBC. Provide an explanation as to which compliance method is being utilized for this project and why it's exempt from fire sprinklers.
-You listed your occupancy type as an R2. Fire sprinklers will need to be installed throughout, IFC 903.2.8
-Install CO detectors, IFC 1103.9 if applicable. Include on drawings.
01/03/2023 Site Engineering REQUIRES RESUBMIT The permit cannot be approved until its associated development package, TD-DEV-1222-00071, has been approved.
12/12/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1122-00166
2835 E Grant Rd. – C-1
Protective Service (1st Review)

TRANSMITTAL: December 12, 2022
This site is located in C-1 Zone (UDC 4.7.20). Protective Service is a permitted use in the zone (Table 4.8-4).

1. As Development Package TD-DEV-1122-00071 has not completed its first review Zoning cannot review this building plan. Zoning will not be able to approve this plan until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/08/2022 PDSD Application Completeness Express REVIEW COMPLETED