Permit Number: TC-COM-1122-00151
Parcel: 13324006E

Address:
207 N MAGUIRE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00151
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Site Zoning APPROVED
01/03/2023 Site Engineering NOT REQUIRED
01/09/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00151

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
1. Conditionally approved, per the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
DENIED
1. The "General Building Summary" table indicates the presence of non-separated mix use. However, none of the information for the other use has been provided. Additionally, it appears that the other use will be an assembly space. In accordance with Section 508.3.2 states that the allowable building area, height and number of stories of the building or portion thereof shall be based on the most restrictive allowances for the occupancy groups under consideration for the type of construction of the building in accordance with Section 503.1. That information has not been provided. Provide detailed information regarding the non separated mix use in accordance with Section 508.3.2.
2. The occupant load calculation is incomplete. There are uses other than business present. Provide a space by space occupant load calculation in accordance with Section 1004.3.
3. No egress plans have been provided for the remodeled space. Provide detailed egress plans.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
1. Conditionally approved, per the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


ELECTRICAL REVIEW COMMENTS
CONDITIONALLY APPROVED
1. Conditionally approved, per the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.



PLUMBING REVIEW COMMENTS:
CONDITIONALLY APPROVED
1. Conditionally approved, per the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/04/2023 Fire New Construction REQUIRES RESUBMIT Occupant load on sheet A1.0 is for a mercantile (M) occupancy and not a B Occupancy

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
12/08/2022 PDSD Application Completeness REVIEW COMPLETED