Permit Number: TC-COM-1122-00122
Parcel: 11706168A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00122
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2022 Site Engineering APPROVED
11/22/2022 Site Zoning APPROVED
12/07/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/29/2022 Commercial Structural REQUIRES RESUBMIT 1. Provide a registrant stamped site plan, floor plan, egress plan, and complete code analysis including construction type, occupancy classification, automatic sprinkler requirements, and the total SF of each identified space.
12/07/2022 Fire New Construction REQUIRES RESUBMIT Need to have drawings that show the change of occupancy, exiting and the new occupant load.
Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
11/17/2022 PDSD Application Completeness REVIEW COMPLETED