Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00111
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/08/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/08/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Exhaust of environmental air (e.g. domestic kitchen range exhaust) shall be located 3 feet horizontally from operable openings. The proposed exhaust outlets shown on Plan 1/M3.1 are both within 3feet of the operable window. Reference: Sections 401.4 and 501.3.1, IMC 2018. 2. Exhaust openings of environmental air shall be 10 feet from mechanical air intakes. The primary vent terminations shown on Plans 1/M3.2 and 1/M3.3 appear to be within 10 feet of the existing mechanical air intakes. Reference: Section 401.4, IMC 2018. 3. Clarify the intent of the proposed window deflector awnings and present details of the awning construction. Reference: Section 107.2.1, IBC 2018. |
||
05/03/2023 | PDSD Application Completeness | REVIEW COMPLETED |