Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00083
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2022 Commercial Electrical APPROVED
02/02/2023 Commercial Structural APPROVED
12/09/2022 Site Engineering APPROVED
11/22/2022 Site Zoning APPROVED
02/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/29/2022 Commercial Mechanical REQUIRES RESUBMIT 1. Correct the north arrow on the mechanical ceiling plan, 1/M1. Reference: Section 107.2.1, IBC 2018.
2. With the addition of the Type II exhaust for the relocated oven, show that adequate make-up air is being provided to the room so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2018.
12/29/2022 Commercial Plumbing REQUIRES RESUBMIT 1. Correct the north arrows on the plumbing floor plans, 1/P1 and 2/P1. Reference: Section 107.2.1, IBC 2018.
2. Clarify the total load for the existing gas meter; is it really only 237 MBH with a 4” service pipe? Reference: Section 402.2, IFGC 2018.
12/04/2022 Fire New Construction REVIEW COMPLETED
11/21/2022 PDSD Application Completeness Express REVIEW COMPLETED