Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1122-00083
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/30/2022 | Commercial Electrical | APPROVED | |||
02/02/2023 | Commercial Structural | APPROVED | |||
12/09/2022 | Site Engineering | APPROVED | |||
11/22/2022 | Site Zoning | APPROVED | |||
02/02/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
12/29/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Correct the north arrow on the mechanical ceiling plan, 1/M1. Reference: Section 107.2.1, IBC 2018. 2. With the addition of the Type II exhaust for the relocated oven, show that adequate make-up air is being provided to the room so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2018. |
||
12/29/2022 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Correct the north arrows on the plumbing floor plans, 1/P1 and 2/P1. Reference: Section 107.2.1, IBC 2018. 2. Clarify the total load for the existing gas meter; is it really only 237 MBH with a 4” service pipe? Reference: Section 402.2, IFGC 2018. |
||
12/04/2022 | Fire New Construction | REVIEW COMPLETED | |||
11/21/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |