Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1122-00050
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2022 | Site Engineering | NOT REQUIRED | |||
| 12/05/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide compliance with the 2012 Outdoor Lighting Code section 104. Provide compliance with 2017 NEC art 240.4(C) for Electrical Service load feeders. Provide compliance with NEC art 240.87 for Arc Energy Reduction. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson/Pima County Outdoor Lighting Code |
||
| 11/14/2022 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: Wyatt Berger Planner PROJECT: TC-COM-11-22-00050 3321 E Global Lp – I-1 Install generator (1st Review) TRANSMITTAL DATE: November 14, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. As you are proposing a reconfiguration of an area outside a building and proposing to remove one motor vehicle parking space, a development package meeting the minor changes to commercial and industrial sites checklist is required: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The development package is a separate submittal and shall be approved prior to approval of this permit. The development package shall be submitted through the Tucson Development Center Online. If you have any questions about this transmittal, please contact me at Wyatt.Berger@tucsonaz.gov. |
||
| 12/12/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 11/10/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |