Permit Number: TC-COM-1122-00027
Parcel: 107144380

Address:
2583 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1122-00027
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2022 Site Zoning APPROVED
11/28/2022 Site Engineering NOT REQUIRED
11/30/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/30/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1122-00027

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
STRUCTURAL APPROVED PENDING FIELD INSPECTOR'S REVIEW OF THE EXISTING STRUCTURE


BUILDING REVIEW COMMENTS:
Denied
NEED THE ELEVATION VIEWS, BUILDING AND SPACE DIMENSIONS, LABEL USES OF ALL SPACES AND INCLUDE TABLES AND CHAIR IF APPLICABLE. TABLE 1004.5 CALCULATES ASSEMBLY AREAS FOR THE JUICE BAR AT 1:15 SF IF TABLES AND CHAIRS ARE INSTALLED, FOR OTHER AREAS, 1:7 SF OR 1:5 SF ARE TO BE USED WHICH WILL INCREASE THE OCCUPANT LOAD AND DETERMINE THE USE GROUP.
ACCESSIBILITY DETAILS OF THE SIGNAGE, ROUTE, TOILET STALL SPACES, SHOWERS, LAVATORIES, BAR SINK, MIRRORS, ETC. NOT SHOWN.
SHOW STAIR/HANDRAIL DETAILS MEETING THE REQUIREMENTS OF SECTIONS 1009, 1011, AND 1014.
SHOW ALL MEANS OF EGRESS LIGHTING FOR EXIT DISCHARGES, ALL INTERIOR SPACES, AND STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS.
INCLUDE EXIT SIGNS AT ALL MEANS OF EGRESS.
IPC SECTION 403.2 REQUIRES SEPARATE TOILET/SHOWER FACILITIES FOR EACH SEX


MECHANICAL REVIEW COMMENTS:
Denied
IPC SECTION 403.2 REQUIRES SEPARATE TOILET/SHOWER FACILITIES FOR EACH SEX AND REVISED MECHANICAL PLANS WILL BE NEEDED.


ELECTRICAL REVIEW COMMENTS
Denied
SHOW ALL MEANS OF EGRESS LIGHTING FOR EXIT DISCHARGES, ALL INTERIOR SPACES, AND STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS PER SECTIONS 1008 AND 1008.3.
INCLUDE EXIT SIGNS AT ALL MEANS OF EGRESS.
THE WATER HEATER SHOWN ON THE PLUMBING PAGES SHOWS 208V/3 PHASE WHICH DOES NOT MATCH THE ELECTRICAL SCHEDULES.
AMENDED IPC SECTION 412.11 REQUIRES AUTOMATIC FAUCETS.


PLUMBING REVIEW COMMENTS:
Denied
IPC SECTION 403.2 REQUIRES SEPARATE TOILET/SHOWER FACILITIES FOR EACH SEX.
NUMBER OF PLUMBING FIXTURES MAY CHANGE IF THE OCCUPANT LOAD IS INCREASED, ACCESSIBILITY DETAILS OF THE SIGNAGE, ROUTE, TOILET STALL SPACES, SHOWERS, LAVATORIES, BAR SINK, MIRRORS, ETC. NOT SHOWN.
AMENDED IPC SECTION 412.11 REQUIRES AUTOMATIC FAUCETS.
SHOW DRINKING FOUNTAINS, WATER COOLERS, OR SOURCE OF FREE DRINKING WATER REQUIRES BY IPC SECTION 410.4
THE WATER HEATER SHOWN ON PAGE P4.0 SHOW IT IS 208V/3 PHASE BUT THE SERVICE IS 120/240V SINGLE PHASE AND IS SUPPLIED BY A 240V CIRCUIT.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/26/2022 Fire New Construction REVIEW COMPLETED
11/03/2022 PDSD Application Completeness Express REVIEW COMPLETED Contractor required prior to issuance