Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1026-01741
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2026 | Commercial Building | APPROVED | |||
| 11/02/2026 | Commercial Electrical | APPROVED | Approved with notes added to plans: Provide a GFCI [NEC 210.8(E)] receptacle outlet on the same level within 25’ of all HVAC units [NEC 210.63(B)(1)]. |
||
| 11/05/2026 | Site Zoning | APPROVED | |||
| 11/05/2026 | Water - PDSD | APPROVED | |||
| 11/05/2026 | Commercial Plumbing | NOT REQUIRED | |||
| 10/27/2026 | Site Engineering | NOT REQUIRED | |||
| 11/10/2026 | Commercial Post Review Express | PENDING ASSIGNMENT | |||
| 11/05/2026 | Commercial Mechanical | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1026-01741 ADDRESS/PARCEL: 9050 E VALENCIA RD TUCSON, AZ 85747 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please provide heating and cooling load calculations to justify the need for the additional mini split unit. Reference: Section C403.1.1 and C502.3.3, IECC 2024. |
||
| 11/10/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 10/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |