Permit Number: TC-COM-1026-01677
Parcel: 14042025A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01677
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2026 Commercial Building Standard APPROVED
11/03/2026 Water - PDSD Standard APPROVED
10/30/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/20/2026 Site Engineering Standard NOT REQUIRED
11/06/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/30/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01677 (2717 E CORONA RD Unit:UNIT 190 TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Please specify the use of the Tech Bays, Tooling/Machining, Battery Changing and Pressure Wash area. This space should be designated as garage space and or vehicle repair space per NEC definitions and use.
2. Classified area documentation requirements per NEC 500.4
500.4 Documentation.
Areas designated as hazardous (classified) locations or determined to be unclassified shall be documented on an area classification drawing and other associated documentation. This documentation shall be available to the authority having jurisdiction (AHJ) and those authorized to design, install, inspect, maintain, or operate electrical equipment at the location.


3. The entire vehicle main bay and repair areas are garage spaces and shall be provided with GFCI protection per NEC 210.8(B)(10).
4. Show hazardous classifications for all vehicle repair garages and storage areas per NEC 511. This area is required to be classified if Class 1 liquids or gaseous fuels are stored, handled, or transferred.
5. The storage or distribution of Class 1 liquids or gaseous fuels would require these spaces to be classified per NEC 511. Note any chemicals, fluids or fuels that may be used during normal operations of this space.
6. Provide a conduit seal detail for electrical pasting through or into a classified area.
7. Provide GFCI, NEC 210.8(D)(3), for the Pressure washer OUTLET.
8. Provide GFCI protection for all receptacles within the area of the welder unit, E6, per NEC 630.8.
11/03/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01677
ADDRESS/PARCEL: 2717 E CORONA RD Unit:UNIT 190 TUCSON, AZ 85756

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide ventilation calculations demonstrating compliance with the minimum outdoor air and exhaust ventilation requirements. The tech bays and wash bay appear to represent a repair garage occupancy in addition to warehouse storage and should be identified and accounted for accordingly in the ventilation calculations. Please also clarify how the ventilation system prevents recirculation of air from the repair garage into other spaces. Reference: Table 403.3.1.1, IMC 2024.
11/03/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01677
ADDRESS/PARCEL: 2717 E CORONA RD Unit:UNIT 190 TUCSON, AZ 85756

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. A separate submittal to Pima County Industrial Wastewater Control is required for new sand/oil separators. Please submit the proposed installation to the County for review and approval. For additional information, contact Kelsey.McMonagle@pima.gov, Fernando.Orduna@pima.gov, or Ann.Gurr@pima.gov.
11/04/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-1026-01677 – Commercial – T.I. of one leasable suite in an industrial shell building
2717 E CORONA RD Unit 190 TUCSON, AZ 85756 (I-1 Zoning)
Commercial Review – 1st Review

TRANSMITTAL DATE:
November 04, 2026

1. COMMENT: When a tenant improvement permit comes in for a change of use, it may continue as a building permit only if the applicant can demonstrate that the available parking on site can accommodate all of the parking requirements of the existing users on that site. Typically, this is shown with an updated parking calculations table and listing of all of the uses on site; vacant suites can be parked at 1/1000 per DP22-0214. If the calculation shows that insufficient parking is available, we may require a development package in addition to the building permit, a revision to DP22-0214 to show where the additional parking will be provided, or an Individual Parking Plan (IPP) to reduce the minimum required amount of parking may be pursued. Provide a parking table that depicts all the existing users, their uses and associated square footage of the uses to verify the approved parking for DP22-0214 is being met (or not).

2. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

3. COMMENT: Corrected commercial permit.

4. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
11/06/2026 Fire New Construction Standard REVIEW COMPLETED
10/16/2026 PDSD Application Completeness Express REVIEW COMPLETED