Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-1024-02095
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/09/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 6/6/2025 10:54:16 PM 1. E1.0 / Power Plan – Bldg 2711 / Service entrance location does not match ES1.0: Service entrance is shown North in ES1.0 but East in E1.0 Power Plan – Bldg 2711. Clarify the location of new service entrance and main distribution switch board. Show the electrical scope in both ES1.0 and E1.0. |
||