Permit Number: TC-COM-1024-02092
Parcel: 10411433A

Address:
4342 N WEGNER LN

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1024-02092
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/07/2025 Commercial Building Standard REQUIRES RESUBMIT October 7, 2025
1st Review

Robert Page, Architect
Attn: Robert Page
4115 W. Granite Dells Ct.
Tucson, Arizona 85745

Re: THE SPECIALIST VEHICLE STORAGE
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-1024-02092
Stantec Project Number: 185215066
Stantec File Number: TUC-25-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 6,424 278 Yes No
Separate Permits: None.
Deferred Submittals: Pre-engineered metal building.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding.

ARCHITECTURAL COMMENTS

Sheet 1.5

1. The 2nd floor ceiling framing plan has not been revised for the new layout of the mezzanine. Please revise the plan accordingly to correlate with the new layout of the mezzanine.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/07/2025 Commercial Electrical Standard REQUIRES RESUBMIT October 7, 2025
1st Review

Robert Page, Architect
Attn: Robert Page
4115 W. Granite Dells Ct.
Tucson, Arizona 85745

Re: THE SPECIALIST VEHICLE STORAGE
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-1024-02092
Stantec Project Number: 185215066
Stantec File Number: TUC-25-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 6,424 278 Yes No
Separate Permits: None.
Deferred Submittals: Pre-engineered metal building.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding.

ARCHITECTURAL COMMENTS

Sheet 1.5

1. The 2nd floor ceiling framing plan has not been revised for the new layout of the mezzanine. Please revise the plan accordingly to correlate with the new layout of the mezzanine.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/07/2025 Commercial Mechanical Standard REQUIRES RESUBMIT October 7, 2025
1st Review

Robert Page, Architect
Attn: Robert Page
4115 W. Granite Dells Ct.
Tucson, Arizona 85745

Re: THE SPECIALIST VEHICLE STORAGE
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-1024-02092
Stantec Project Number: 185215066
Stantec File Number: TUC-25-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 6,424 278 Yes No
Separate Permits: None.
Deferred Submittals: Pre-engineered metal building.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding.

ARCHITECTURAL COMMENTS

Sheet 1.5

1. The 2nd floor ceiling framing plan has not been revised for the new layout of the mezzanine. Please revise the plan accordingly to correlate with the new layout of the mezzanine.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/07/2025 Commercial Plumbing Standard REQUIRES RESUBMIT October 7, 2025
1st Review

Robert Page, Architect
Attn: Robert Page
4115 W. Granite Dells Ct.
Tucson, Arizona 85745

Re: THE SPECIALIST VEHICLE STORAGE
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-1024-02092
Stantec Project Number: 185215066
Stantec File Number: TUC-25-095

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
S-1 II-B 6,424 278 Yes No
Separate Permits: None.
Deferred Submittals: Pre-engineered metal building.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding.

ARCHITECTURAL COMMENTS

Sheet 1.5

1. The 2nd floor ceiling framing plan has not been revised for the new layout of the mezzanine. Please revise the plan accordingly to correlate with the new layout of the mezzanine.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/03/2025 PDSD Application Completeness Express REVIEW COMPLETED