Permit Number: TC-COM-1024-02092
Parcel: 10411433A

Address:
4342 N WEGNER LN

Review Status: Requires Resubmit

Review Details: SPECIAL INSPECTION REVIEW v.2

Permit Number - TC-COM-1024-02092
Review Name: SPECIAL INSPECTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/22/2026 Special Inspection Certificate Review (Deferred Submittal) Express REQUIRES RESUBMIT Special Inspection Certificate Review
TC-COM-1024-02092 (4342 N WEGNER LN TUCSON, AZ 85705)

1. Please resubmit the Building Special Inspection Certificate, along with the associated field reports. This Building Special Inspection Certificate has the incorrect address and needs to match the permit address and the address on the field reports.
2. The provided Outdoor Lighting Special Inspection Certificate is missing the Date Signed by the EOR. Please resubmit the ODL SI Cert, with a corrected Registrant’s Seal, to include the date signed.
A signature and date are required as part of the Registrant Seal (Electrical). Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration states that in addition to signing the seal, the registrant shall include the date the document was signed. The EOR seal is missing the date signed.
07/22/2026 Concrete Installation Inspection (Deferred Submittal) Express REVIEW COMPLETED
07/22/2026 Other Inspection Reports (Deferred Submittal) Express REVIEW COMPLETED
07/22/2026 PDSD Application Completeness Express REVIEW COMPLETED
07/22/2026 Post-Installed Anchor Inspection (Deferred Submittal) Express REVIEW COMPLETED
07/22/2026 Welding Inspection (Deferred Submittal) Express REVIEW COMPLETED