Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1024-02092
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2025 | Water - PDSD | APPROVED | |||
| 01/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/10/2024 | Commercial Electrical | REQUIRES RESUBMIT | December 10, 2024 2nd Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. Sheet 0.1 1. Previous Comment: Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: High-strength bolts is not noted on the cover page of the revised plan-set. Revised Sheet SE1 now indicates that outdoor lighting special inspection is required. Please be sure to update the cover page to reflect this special inspection as well and submit a special inspection certificate with Parts A and B completed for outdoor lighting. Sheet C4 1. Addressed. 2. Previous Comment: Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} New Comment: The site plan was revised with the latest submittal to include the site private sewer lines but does not include the underground gas lines and is noted that the site utilities will be submitted under a separate submittal. The electrical drawings include the electrical site utilities as well. Please clarify on the site plan which utilities will be submitted under a separate permit and update the plans accordingly (i.e. remove the site utilities from the plan-set if being applied for under a separate permit.). Please also remove the “For Reference Only” note on the site plan as this sheet is being used for building code compliance. Sheet 1.4 1. Addressed. Sheet 1.5 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/10/2024 | Commercial Mechanical | REQUIRES RESUBMIT | December 10, 2024 2nd Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. Sheet 0.1 1. Previous Comment: Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: High-strength bolts is not noted on the cover page of the revised plan-set. Revised Sheet SE1 now indicates that outdoor lighting special inspection is required. Please be sure to update the cover page to reflect this special inspection as well and submit a special inspection certificate with Parts A and B completed for outdoor lighting. Sheet C4 1. Addressed. 2. Previous Comment: Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} New Comment: The site plan was revised with the latest submittal to include the site private sewer lines but does not include the underground gas lines and is noted that the site utilities will be submitted under a separate submittal. The electrical drawings include the electrical site utilities as well. Please clarify on the site plan which utilities will be submitted under a separate permit and update the plans accordingly (i.e. remove the site utilities from the plan-set if being applied for under a separate permit.). Please also remove the “For Reference Only” note on the site plan as this sheet is being used for building code compliance. Sheet 1.4 1. Addressed. Sheet 1.5 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/10/2024 | Commercial Plumbing | REQUIRES RESUBMIT | December 10, 2024 2nd Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. Sheet 0.1 1. Previous Comment: Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: High-strength bolts is not noted on the cover page of the revised plan-set. Revised Sheet SE1 now indicates that outdoor lighting special inspection is required. Please be sure to update the cover page to reflect this special inspection as well and submit a special inspection certificate with Parts A and B completed for outdoor lighting. Sheet C4 1. Addressed. 2. Previous Comment: Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} New Comment: The site plan was revised with the latest submittal to include the site private sewer lines but does not include the underground gas lines and is noted that the site utilities will be submitted under a separate submittal. The electrical drawings include the electrical site utilities as well. Please clarify on the site plan which utilities will be submitted under a separate permit and update the plans accordingly (i.e. remove the site utilities from the plan-set if being applied for under a separate permit.). Please also remove the “For Reference Only” note on the site plan as this sheet is being used for building code compliance. Sheet 1.4 1. Addressed. Sheet 1.5 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/10/2024 | Commercial Structural | REQUIRES RESUBMIT | December 10, 2024 2nd Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. Sheet 0.1 1. Previous Comment: Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: High-strength bolts is not noted on the cover page of the revised plan-set. Revised Sheet SE1 now indicates that outdoor lighting special inspection is required. Please be sure to update the cover page to reflect this special inspection as well and submit a special inspection certificate with Parts A and B completed for outdoor lighting. Sheet C4 1. Addressed. 2. Previous Comment: Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} New Comment: The site plan was revised with the latest submittal to include the site private sewer lines but does not include the underground gas lines and is noted that the site utilities will be submitted under a separate submittal. The electrical drawings include the electrical site utilities as well. Please clarify on the site plan which utilities will be submitted under a separate permit and update the plans accordingly (i.e. remove the site utilities from the plan-set if being applied for under a separate permit.). Please also remove the “For Reference Only” note on the site plan as this sheet is being used for building code compliance. Sheet 1.4 1. Addressed. Sheet 1.5 1. Addressed. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Addressed. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/27/2024 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1024-02092 4342 N WEGNER LN Site engineering comments are as follows: The Engineering comments from the previous review cycle still apply: 1. The entitlements case TP-ENT-1024-00021 must be approved before DP21-0261 can be approved. 2. DP21-0261 must be approved before this building permit can be approved. Ryan Insalaco – ryan.insalaco@tucsonaz.gov |
||
| 12/30/2024 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Fernando Garcia Planning & Development Services Department – Zoning Review Section PROJECT: TC-COM-1024-02092 – Commercial Building (ref. DP21-0261) 4342 N Wegner Ln, Tucson, AZ 85705 Plan Review (2nd Review) TRANSMITTAL DATE: December 30, 2024 This site is zoned MU (UDC Section 4.7.23). Commercial storage is an approved used in this zone subject to use-specific standard 4.9.10.A and contingent upon a Zoning Examiner Special Exception. 1. (Comment) Although the plans appears to match, final Site Zoning approval of this plan cannot occur until development package, DP21-02612, is approved. Once approved, please resubmit the building permit. Ensure the building permit documents match the approved development package (for example, inclusion, of new shade structures). RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approval of DP21-0261 and resubmittal of revised plans. If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov. |
||
| 12/06/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |