Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1024-02092
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/18/2024 | Commercial Electrical | REQUIRES RESUBMIT | November 12, 2024 1st Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. All sheets within the plan-set are not to the indicated scales shown on each sheet. Please revise. 2. Please provide an energy conservation compliance report for the building thermal envelope. [Ref. IECC 2018 Sec. C402] Sheet 0.1 1. Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet C1 1. Please provide on the site plan the following information: a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705]. b. The buildings finish floor elevation(s) [2018 IPC Sec. 714]. c. On-site private water line(s), including domestic, fire, and irrigation, from the building to the public utility meter(s), including any required backflow prevention [2018 IPC Sec. 608]. d. On-site private sewer line(s) from the building to the public sewer, including the rim height of the upstream manhole in the private and public sewer lines [2018 IBC Sec. 714]. e. Please also be sure that this sheet is signed by the registrant and remove for reference only if being used for site utilities. 2. Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} Sheet 1.4 1. The mezzanine bathroom indicates a shower. The only bathing facility in the building is located on an inaccessible floor. Please remove the shower from the inaccessible mezzanine or add an accessible shower to the first floor. [Ref. IBC 2018 Sec. 1109.2] Sheet 1.5 1. Please provide descriptions for keynotes 15 & 16 on the wall section details 1 & 2. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Please provide on the plans a statement that special inspection is required (or is not required) for outdoor lighting. [Ref. 2012 City of Tucson Outdoor Lighting Code Sec. 104.2.2.] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 11/18/2024 | Commercial Mechanical | REQUIRES RESUBMIT | November 12, 2024 1st Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. All sheets within the plan-set are not to the indicated scales shown on each sheet. Please revise. 2. Please provide an energy conservation compliance report for the building thermal envelope. [Ref. IECC 2018 Sec. C402] Sheet 0.1 1. Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet C1 1. Please provide on the site plan the following information: a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705]. b. The buildings finish floor elevation(s) [2018 IPC Sec. 714]. c. On-site private water line(s), including domestic, fire, and irrigation, from the building to the public utility meter(s), including any required backflow prevention [2018 IPC Sec. 608]. d. On-site private sewer line(s) from the building to the public sewer, including the rim height of the upstream manhole in the private and public sewer lines [2018 IBC Sec. 714]. e. Please also be sure that this sheet is signed by the registrant and remove for reference only if being used for site utilities. 2. Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} Sheet 1.4 1. The mezzanine bathroom indicates a shower. The only bathing facility in the building is located on an inaccessible floor. Please remove the shower from the inaccessible mezzanine or add an accessible shower to the first floor. [Ref. IBC 2018 Sec. 1109.2] Sheet 1.5 1. Please provide descriptions for keynotes 15 & 16 on the wall section details 1 & 2. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Please provide on the plans a statement that special inspection is required (or is not required) for outdoor lighting. [Ref. 2012 City of Tucson Outdoor Lighting Code Sec. 104.2.2.] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 11/18/2024 | Commercial Plumbing | REQUIRES RESUBMIT | November 12, 2024 1st Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. All sheets within the plan-set are not to the indicated scales shown on each sheet. Please revise. 2. Please provide an energy conservation compliance report for the building thermal envelope. [Ref. IECC 2018 Sec. C402] Sheet 0.1 1. Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet C1 1. Please provide on the site plan the following information: a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705]. b. The buildings finish floor elevation(s) [2018 IPC Sec. 714]. c. On-site private water line(s), including domestic, fire, and irrigation, from the building to the public utility meter(s), including any required backflow prevention [2018 IPC Sec. 608]. d. On-site private sewer line(s) from the building to the public sewer, including the rim height of the upstream manhole in the private and public sewer lines [2018 IBC Sec. 714]. e. Please also be sure that this sheet is signed by the registrant and remove for reference only if being used for site utilities. 2. Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} Sheet 1.4 1. The mezzanine bathroom indicates a shower. The only bathing facility in the building is located on an inaccessible floor. Please remove the shower from the inaccessible mezzanine or add an accessible shower to the first floor. [Ref. IBC 2018 Sec. 1109.2] Sheet 1.5 1. Please provide descriptions for keynotes 15 & 16 on the wall section details 1 & 2. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Please provide on the plans a statement that special inspection is required (or is not required) for outdoor lighting. [Ref. 2012 City of Tucson Outdoor Lighting Code Sec. 104.2.2.] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 11/18/2024 | Commercial Structural | REQUIRES RESUBMIT | November 12, 2024 1st Review Robert Page, Architect Attn: Robert Page 4115 W. Granite Dells Ct. Tucson, Arizona 85745 Re: THE SPECIALIST VEHICLE STORAGE NEW BUILDING City of Tucson Permit Number: TC-COM-1024-02092 Stantec Project Number: 185215066 Stantec File Number: TUC-24-136 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms S-1 II-B 6,424 278 Yes No Separate Permits: None. Deferred Submittals: Pre-engineered metal building. Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, and field welding. ARCHITECTURAL COMMENTS General 1. All sheets within the plan-set are not to the indicated scales shown on each sheet. Please revise. 2. Please provide an energy conservation compliance report for the building thermal envelope. [Ref. IECC 2018 Sec. C402] Sheet 0.1 1. Note on the cover of the drawings that special inspection is required for high-strength bolts. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet C1 1. Please provide on the site plan the following information: a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705]. b. The buildings finish floor elevation(s) [2018 IPC Sec. 714]. c. On-site private water line(s), including domestic, fire, and irrigation, from the building to the public utility meter(s), including any required backflow prevention [2018 IPC Sec. 608]. d. On-site private sewer line(s) from the building to the public sewer, including the rim height of the upstream manhole in the private and public sewer lines [2018 IBC Sec. 714]. e. Please also be sure that this sheet is signed by the registrant and remove for reference only if being used for site utilities. 2. Please clarify on the site plan if the private site utilities are part of this permit or are under a separate permit. {An approved development plan does not constitute a building permit to build private site utilities; on-site private utilities need to be submitted as part of this permit or under a separate permit.} Sheet 1.4 1. The mezzanine bathroom indicates a shower. The only bathing facility in the building is located on an inaccessible floor. Please remove the shower from the inaccessible mezzanine or add an accessible shower to the first floor. [Ref. IBC 2018 Sec. 1109.2] Sheet 1.5 1. Please provide descriptions for keynotes 15 & 16 on the wall section details 1 & 2. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS General 1. Please provide on the plans a statement that special inspection is required (or is not required) for outdoor lighting. [Ref. 2012 City of Tucson Outdoor Lighting Code Sec. 104.2.2.] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 11/15/2024 | Site Engineering | REQUIRES RESUBMIT | 1. The entitlements case TP-ENT-1024-00021 must be approved before DP21-0261 can be approved. 2. DP21-0261 must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
| 11/26/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-1024-02092 - DP21-0261 4342 N WEGNER LN. – MU Commercial Storage (1st Review) TRANSMITTAL DATE: November 26, 2024 Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the MU zone (UDC 4.7.23). Commercial Storage is an allowed use in the zone (UDC Table 4.8-7), subject to a Zoning Examiner Special Exception Procedure, Section 3.4.3 and Use Specific Standard 4.9.10.A. 1. Zoning has reviewed the building plans for compliance with Development Package (DP) DP21-0261 and although it appears the plans are consistent with each other until the DP is approved by all review agencies Zoning cannot approve this building permit. 2. Any DP sheets submitted within the building plan set shall either be the stamped approved sheets or marked for reference only. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 11/26/2024 | Water - PDSD | REQUIRES RESUBMIT | Show the location and size of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018. | ||
| 11/15/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 10/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |