Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1024-02030
Parcel: 10509553A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-02030
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2024 Water - PDSD APPROVED CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)
11/07/2024 Site Engineering NOT REQUIRED CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)
11/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)
11/12/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)



Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 11/6/2024 6:24:04 PM





Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 11/8/2024 1:15:32 AM
All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block of the sheet. As part of the resubmittal, please collate all revised sheets into the electronic document (PDF) and submit a complete and
full plan set. We cannot accept individual sheets in response to review comments, since the entire plan set is required for approval and permitting.
Please include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to each of the noted plan review comments items.
Provide a copy of the Special Inspections and Schedule of Special Inspection Services forms that are completed, signed and sealed by the project engineer. 2018 IBC Section 1704.2.1.
1. Sheet A6.1 (Enlarged RR Plans & Elevations First Floor Restrooms). Indicate the required 60” turning space within the Men’s RR 1604 and Women’s RR 1603 on the Lobby Restrooms & Staff Shower enlarged floor plan. ICCI A117.1-
2009 Section 304.3.1.




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 11/11/2024 12:15:04 PM
1. Plan Sheet M1.1S - VAV 3-1-21 supply air drop CFM total is 1275 CFM. Plan sheet M5.2 states under EXISTING PAC
3 - VAV BOX SCHEDULE (FIRST FLOOR) VAV 3-1-21 total CFM is 825 CFM. Confirm CFM for VAV 3-1-21. - 2018 IECC Section C103.2Information on construction document - 2018 IBC – Section [A]107.2.1Information on construction documents.
2. Plan sheet M1.2N - VAV 1-2-4 Identify all supply type, of air device. - 2018 IECC Section C103.2Information on construction document - 2018 IBC – Section [A]107.2.1Information on construction documents.




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/31/2024 4:16:20 PM
Electrical Review of El Rio Health Clinic Suit 120
1. EP102S NEW POWER PLAN - SECOND FLOOR SOUTH could not locate Equipment Note 8, panel 2LE1.
2. EP201S NEW HVAC POWER PLAN - FIRST FLOOR SOUTH could not locate Equipment Note 1, panel LSO2.
3. Feeders imply that the CBs should be 200 amp.
4. EP601 PANEL SCHEDULES has undersized 20 amp circuit breaker in panel H2OS2 for CRAC-3 unit. Will nuisance trip.
5. EP602 PANEL SCHEDULES all 30-amp twist locks in panels LV1A and LV2A have undersized circuit breakers for shown load of 5 KW. Will nuisance trip all loaded circuit breakers. Update/reduce load or upsize circuit breakers to 30 amp. Sterilizer CB 49,51 and conductor are undersized in panel LV7.
6. EP603 PANEL SCHEDULES all 30-amp twist locks in panel 2LV1 have undersized circuit breakers for shown load of
5 KW. Will nuisance trip all loaded circuit breakers. Update/reduce load or upsize circuit breakers to 30 amp.
7. EP604 PANEL SCHEDULES panel 2LOS2 may nuisance trip CB 37,39,41 in panel 2LOS1. Should upsize 60 amp CB and conductors or re-evaluate load on 2LOS2 panel.
8. EP604 PANEL SCHEDULES has undersized 20 amp circuit breakers in panel UPS1 for sub panels 2UPS1 and UPS2. Feeders imply that the CBs should be 150 amp.
9. EP604 PANEL SCHEDULES all 30-amp twist locks in all UPS panels have undersized circuit breakers for shown load of 5 KW. Will nuisance trip all loaded circuit breakers. Update-reduce load or upsize circuit breakers to 30 amp.
10. EP701 SINGLE LINE DIAGRAM comment only, some 100 amp circuit breakers in new MSB ‘SES-1’ are smaller than original 150 amp circuit breakers in original MSB ‘MSA’.
11. EP702 SINGLE LINE DIAGRAM coordinate any changes in panel feeds on EP604 ie Panel feed from 2LOS1 to 2LOS2.






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/10/2024 8:53:27 PM
First Plumbing Review: Suite 120
1). Plan Pages P4.1 & P5.1: Vacuum Exhaust & fresh air intake need to maintain 25ft separation. Update illustrations to show Vacuum Exhaust & fresh air intake maintaining 25ft separation. -2018 NFPA99 5.1.3.7.7.2
2). Plan Page P7.1: Waste Stack Detail # 4, Waste needs to remain 3" thru roof level. Update Waste Stack Detail # 4, to waste remaining remain 3" thru roof level. -2018 IPC 913.4
3). Plan Page P3.1S: Missing gas piping illustrations & information for the gas water heaters. Add gas piping illustrations & information for gas water heaters.-2018 IFGC 106.31, 402.3.
4). Plan Pages P4.1 & P7.5: Missing Gas water heater exhaust & combustion Air illustrations & information. Add Gas water heater exhaust & combustion Air illustrations & information. -2018 IFGC 304, 503.1
11/18/2024 Site Zoning REQUIRES RESUBMIT CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)

FROM: PDSD Zoning Review

PROJECT: TC-COM-1024-02030 & TC-COM-1024-02031 - TD-DEV-0824-00238
4888 N STONE AV. – C-1/C-2
Medical Service: Outpatient, excluding blood donor centers ( Review)

TRANSMITTAL DATE: November 18, 2024

Resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Medical Service: Outpatient is a permitted uses in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.O.2, 4.9.13.O and 4.9.13.P

1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0824-00238 an although the plans appear to match until the DP is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/07/2024 Fire New Construction REVIEW COMPLETED CONNECTED PLAN REVIEW: MASTER SET OF PLANS ON TC-COM-1024-02030 (4888 N STONE AV Unit:UNIT 120) WITH REVIEW COMMENTS TO BE COPIED TO TC-COM-1024-02031 (4888 N STONE AV Unit:UNIT 180)
10/24/2024 PDSD Application Completeness REVIEW COMPLETED