Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1024-01978
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2024 | Commercial Mechanical | APPROVED | Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 12/10/2024 10:52:29 AM |
||
| 12/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/11/2024 | Commercial Structural | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 12/11/2024 4:18:04 PM Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/4/2024 7:17:58 AM 1. Sheet TS1 – Deferred submittal lists NFPA “13R” fire sprinkler and sprinkler monitoring systems. NFPA 13R is a residential sprinkler design standard focused on low-rise residential occupancies not for business occupancy use. (Closed) 2. TS1 – Describe the scope of fire alarm system if any. (Closed) 3. TS1 – General notes indicate “2000” IBC series which are not applicable for City of Tucson. (Closed) 4. Accessibility details such as floor clearances missing that should comply with 2009 ICC/ANSI-A117.1. (Closed) 5. A7.1 – Shows W8x31 steel beam but missing structural foundation plan and details. Show support of this beam and connections. (Closed) 6. A3 – Missing method of roof access. Show how the roof is accessed to the mechanical appliances. (Closed) 7. A1.1 – 2018 International Fire Code section 901.4.6.4 Lighting. Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms. Light missing in RCP. Sheet A2 missing in resubmission. 8. A1.1 – 2018 IFC section 901.4.6 pump and riser roof size. The riser rooms shall be designed with adequate space for all equipment necessary for installation, as defined by the manufacturer, with sufficient working space around the stationary equipment. F.R 116 is not shing this clearance space. (Closed) 9. TS1 sheet index shows 30 pages of design documents but only 16 pages were provided. Please resubmit complete construction documents for release of construction set. (2018 IBC section 107.2.1.) |
||
| 12/20/2024 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1024-01978 2562 N ALVERNON WY Site engineering comments are as follows: 1. Sheet TS1: The North Arrow on the Exiting Plan is pointed to the east. Ryan Insalaco ryan.insalaco@tucsonaz.gov |
||
| 12/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 12/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |