Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1024-01962
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/30/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Janet Matz jmatz@safebuilt.com Denied Reason: Date Completed : 1/30/2025 5:57:16 PM 1. UNRESOLVED. Sheet GI001 / Deferred Submittals / missing submittal. The deferred submittals does not include the alarm system for the medical gas alarm system. Revise the deferred submittal notes to include the medical gas alarm system as a deferred submittal; or, if the medical gas alarm system is integrated with the fire alarm system, revise the notes to include the deferred fire alarm system is integral to the medical gas alarm system. (2018 NFPA 99 - 5.1.9.1). ◦ CLARIFICATION: A response narrative was not provided and it is not clear how this was resolved. ◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans. 9. UNRESOLVED. Sheet MG001 / Medical Gas Schedules / missing manufacturer & model. Revise the medical gas schedules to include the manufacturer and model for the medical gas alarm panels, zone valve boxes, and gas outlets. (2018 NFPA 99 - 5.1.4). ◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information. ◦ Partially Resolved. It appears only the Medical Gas Alarm Panel information was added. Include the zone valve boxes and gas outlets information on the drawing. 10. UNRESOLVED. Sheet MG001 / Medical Gas Zone Valve Box Schedule / missing details. Revise the plans to include a graphic detail showing the required labelling of zone valve box with the contained in the provided code section. (2018 NFPA 99 - 5.1.4.1.3). ◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information. ◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans. 11. UNRESOLVED. Sheet MG201 / Medical Gas Plan / missing area alarm information. The floor plans show the routing of the medical gas piping, but do not include the location of the area medical gas area alarm panel. (2018 NFPA 99 - 5.1.9.4). ◦ CLARIFICATION: The response narrative references sheet MG201; however, the location of the alarm panel is not clearly provided and the response narrative does not indicate a clear location or other information to provide the reviewer with needed information. ◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans. 12. UNRESOLVED. Sheet MG201 / Medical Gas Plan / missing tubing or piping material type. Revise the plans or general notes to include the gas piping or tubing material types. (2018 NFPA 99 - 5.1.10.1). ◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information. ◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans. |
||
01/30/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 1/30/2025 7:50:45 PM Third Plumbing Review: Resolved- 1). Plan Page P001: Missing Plumbing Code Summary: Add plumbing Code Summary. -2018 IPC Unresolved-2). General Med Gas plan pages: Need to address all of the med gas comments listed in the Mechanical Review2018 NFPA99 Resolved-3). Plan P901 Fixture schedule: Lavatory section missing ASSE 1070 Mixing Valve. List the ASSE1070 mixing valve model to be used- 2018 IPC 419.5 |
||
01/28/2025 | Fire New Construction | REVIEW COMPLETED | |||
01/27/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |