Permit Number: TC-COM-1024-01962
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1024-01962
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2025 Commercial Mechanical REQUIRES RESUBMIT Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 1/30/2025 5:57:16 PM
1. UNRESOLVED. Sheet GI001 / Deferred Submittals / missing submittal. The deferred submittals does not include the alarm system for the medical gas alarm system. Revise the deferred submittal notes to include the medical gas alarm
system as a deferred submittal; or, if the medical gas alarm system is integrated with the fire alarm system, revise the notes to include the deferred fire alarm system is integral to the medical gas alarm system. (2018 NFPA 99 - 5.1.9.1).
◦ CLARIFICATION: A response narrative was not provided and it is not clear how this was resolved.
◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans.
9. UNRESOLVED. Sheet MG001 / Medical Gas Schedules / missing manufacturer & model. Revise the medical gas schedules to include the manufacturer and model for the medical gas alarm panels, zone valve boxes, and gas
outlets. (2018 NFPA 99 - 5.1.4).
◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information.
◦ Partially Resolved. It appears only the Medical Gas Alarm Panel information was added. Include the zone valve
boxes and gas outlets information on the drawing.
10. UNRESOLVED. Sheet MG001 / Medical Gas Zone Valve Box Schedule / missing details. Revise the plans to include a graphic detail showing the required labelling of zone valve box with the contained in the provided code section. (2018 NFPA 99 - 5.1.4.1.3).
◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information.
◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans.
11. UNRESOLVED. Sheet MG201 / Medical Gas Plan / missing area alarm information. The floor plans show the routing
of the medical gas piping, but do not include the location of the area medical gas area alarm panel. (2018 NFPA 99 - 5.1.9.4).
◦ CLARIFICATION: The response narrative references sheet MG201; however, the location of the alarm panel is not clearly provided and the response narrative does not indicate a clear location or other information to provide the reviewer with needed information.
◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans.
12. UNRESOLVED. Sheet MG201 / Medical Gas Plan / missing tubing or piping material type. Revise the plans or general notes to include the gas piping or tubing material types. (2018 NFPA 99 - 5.1.10.1). ◦ CLARIFICATION: The response narrative refers back to the specifications manual; however, this does not
address the review comment. It is not efficient, typical, or efficient for the field inspector to review the specifications. Revise the plans (not the specifications) to provide the requested information.
◦ Remains Unresolved. A response narrative was not provided and it is not clear how this was resolved. Information was not found on plans.
01/30/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/30/2025 7:50:45 PM
Third Plumbing Review:
Resolved- 1). Plan Page P001: Missing Plumbing Code Summary: Add plumbing Code Summary. -2018 IPC Unresolved-2). General Med Gas plan pages: Need to address all of the med gas comments listed in the Mechanical Review2018 NFPA99
Resolved-3). Plan P901 Fixture schedule: Lavatory section missing ASSE 1070 Mixing Valve. List the ASSE1070 mixing valve model to be used- 2018 IPC 419.5