Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1024-01962
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1024-01962
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 3/26/2025 12:49:32 AM
The code indicates that the ductwork shall be constructed of sheet steel not less than No. 26 to apply the exception. The use of any flexible ductwork would not be in compliance with this exception. Provide a written interpretation from the International Code Council that the description in the commentary can be used and that no fire damper would be required with the use of flex ducts within the room.
2018 IMC 607.5.2 Fire Barriers Exception 3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are
in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 of the International Building Code. For the purposes of this exception, a ducted HVAC
system shall be a duct system for the structure’s HVAC system. Such a duct system shall be constructed of sheet steel not less than No. 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and
inlet terminals.
03/24/2025 Fire New Construction Standard REVIEW COMPLETED
03/17/2025 PDSD Application Completeness Express REVIEW COMPLETED