Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-1024-01955
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved with Comments Reason: Date Completed : 10/14/2025 8:51:22 AM Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances. |
||
| 10/20/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/13/2025 5:51:16 PM 1. Sheet E802 Riser Note 3 conflicts with Feeder Legend. Comment only, should be corrected for IFC. |
||
| 10/20/2025 | Commercial Mechanical Standard | APPROVED | Mechanical(M) Reviewer Jake Doub jdoub@safebuilt.com Approved Reason: Date Completed : 10/18/2025 6:04:49 PM |
||
| 11/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/20/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 10/17/2025 8:39:39 PM Revised Plumbing Review: 1). Plan Page M801: Missing Combustion Air sizing Calculations adjacent to Intake air Schedule. Add Combustion Air sizing Calculations adjacent to Intake air Schedule. -2018 IFGC 304 |
||
| 10/24/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1024-01955 (1305 S ALVERNON WY TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 2. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. 4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. 5. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Provided light fixtures, WP & WPE, are listed at 4000K color temperature. 6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 7. Specify any exceptions used. 8. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 11/13/2025 | Site Engineering Standard | REQUIRES RESUBMIT | See Zoning comments | ||
| 11/13/2025 | Site Zoning Standard | REQUIRES RESUBMIT | 1. COMMENT: This tenant improvement building permit cannot be used to propose changes to the site that including parking and ADA accessibility. Please include these changes as part of development package, TD-DEV-1025-00255, instead. Contact Fernando Garcia at fernando.garcia2@tucsonaz.gov. |
||
| 10/30/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1024-01955 ADDRESS/PARCEL: (1305 S ALVERNON WY TUCSON, AZ 85711) The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS 1. Please provide the size of the existing water meter (and serial number), the size of the backflow preventer associated with the water meter, and the show the location of the water meter on the site plan. Reference: Section 107.2.1, IBC 2018. |
||
| 10/29/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 10/10/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |