Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1024-01900
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2025 | Commercial Plumbing | APPROVED | |||
| 01/27/2025 | Commercial Structural | APPROVED | |||
| 01/31/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/27/2025 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-1024-01900 (100 S SARNOFF DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). 1. The following comment was not addressed. Fixture QQ is not included in the outdoor lighting lumen calulations: 8 Show the 'LED Band lighting' in the lighting plan and include in the lumen calculations. See plan sheet 'A6' detail 8. The ‘LED Band Lighting’ would not be considered a full cut off lighting fixture and so Option 2 from Table 401.1 wouldn’t apply. 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc . 2. Correct the outdoor lighting calculations to show the correct fixture designations that match the ‘CALLOUT’ on the ‘Luminaire Schedule’. (QQ, R, W, W1). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/31/2025 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1024-01900 100 S SARNOFF DR Site engineering comments are as follows: 1. The associated development package, TD-DEV-1224-00338, must be approved by all reviewers prior to the approval of this permit submission. UDC Article 3.3.3.7.a “The approved site plan on file with the PDSD is the basis for issuance of building permits.” Ryan Insalaco – ryan.insalaco@tucsonaz.gov |
||
| 01/09/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |