Permit Number: TC-COM-1024-01900
Parcel: 134120020

Address:
100 S SARNOFF DR

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-01900
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2024 Site Zoning APPROVED
11/06/2024 Commercial Mechanical NOT REQUIRED
11/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/05/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

1. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

2 See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

3 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc .

4 Provide calculations for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

5 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6 Specify any exceptions used.

7 Provide Curfew lighting controls If applicable Per section 403.
8 Show the 'LED Band lighting' in the lighting plan and include in the lumen calculations. See plan sheet 'A6' detail A.

Do not confuse the Outdoor Lighting Code with the IECC.



Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
11/06/2024 Commercial Plumbing REQUIRES RESUBMIT Provide roof drainage and scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3” per hour. Reference: Sections 1101.7, 1106, and 1108, IPC 2018.
11/01/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Structural Calculations: Please amend calculations to remove Page 5 of the structural Calculations for Project: Dairy Queen Cave Creek and replace the page for Dairy Queen Tucson. IBC 107.2.1 Additionally, Tucson is spelled incorrectly throughout the Calculations as Tuscon.
2. Please amend plans to show code compliant exterior accessible route from the parking lot to the walk-up windows. IBC 1104.1
3. Please amend plans to provide construction drawings and details to indicate the construction, size, and installation fo the roof drainage system. IBC 107.2.1 Additionally, provide roof drainage system calculations to show that the storm drainage will comply with applicable provisions of IPC Chapter 11
4. Please amend plans, to provide sheet A-7 referred by detail 8/A-6 sheet for LED LIGHT BAND
FIXTURE "EE" – RED (SEE SHT. A-7) These light fixtures should be included in the Luminaire Schedule Sheet E2
5. Please amend plans to add note: Signs by Separate Permit. IBC 107.2.1
6. Please provide a statement of special inspections for this project, as well as a list of the required special inspections. IBC 107.2.1, IBC 1704, IBC 1705 For example, Welding, Fabricators

7. Please amend the Special Inspections area to list the required special inspections.
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/05/2024 Site Engineering REQUIRES RESUBMIT 1. A development package is required and must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
10/08/2024 Fire New Construction REVIEW COMPLETED
10/07/2024 PDSD Application Completeness Express REVIEW COMPLETED