Permit Number: TC-COM-1023-02525
Parcel: 13824101L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1023-02525
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2023 Site Zoning APPROVED
11/27/2023 Water - PDSD APPROVED
12/01/2023 Site Engineering NOT REQUIRED
12/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/15/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2023 1:24:30 PM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2023 1:23:04 PM
1) Sheets A1.0 and A2.0: The wall between the x-ray room and the technician area is specified as wall type 1B but this wall type is not included in the plans. (2018 IBC section 107)

2) Sheet A2.0: The wall sections reference a ceiling schedule which is not included in the plans. (2018 IBC section 107)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2023 1:23:53 PM
See the building review comments.




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2023 1:23:41 PM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2023 1:24:08 PM
See the building review comments.
11/29/2023 Fire New Construction REVIEW COMPLETED
11/03/2023 PDSD Application Completeness Express REVIEW COMPLETED