Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1023-02525
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2023 | Site Zoning | APPROVED | |||
| 11/27/2023 | Water - PDSD | APPROVED | |||
| 12/01/2023 | Site Engineering | NOT REQUIRED | |||
| 12/01/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/15/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/14/2023 1:24:30 PM See the building review comments. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/14/2023 1:23:04 PM 1) Sheets A1.0 and A2.0: The wall between the x-ray room and the technician area is specified as wall type 1B but this wall type is not included in the plans. (2018 IBC section 107) 2) Sheet A2.0: The wall sections reference a ceiling schedule which is not included in the plans. (2018 IBC section 107) Mechanical(M) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/14/2023 1:23:53 PM See the building review comments. Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/14/2023 1:23:41 PM See the building review comments. Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 11/14/2023 1:24:08 PM See the building review comments. |
||
| 11/29/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 11/03/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |