Permit Number: TC-COM-1023-02482
Parcel: 115043060

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02482
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2023 Water - PDSD APPROVED -Shared Studio Session 923-111-188 - Master Permit TC-COM-1023-02482 (1131 N 6TH AV TUCSON, AZ 85705)/BLDG 1 Commercial Addition/Alteration Permit AND COVERS IMPROVEMENTS FOR TC-COM-1023-02523 (1131 N 6TH AV TUCSON, AZ 85705) BLDG 2 Commercial New Building Permit
11/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT -Shared Studio Session 923-111-188 - Master Permit TC-COM-1023-02482 (1131 N 6TH AV TUCSON, AZ 85705)/BLDG 1 Commercial Addition/Alteration Permit AND COVERS IMPROVEMENTS FOR TC-COM-1023-02523 (1131 N 6TH AV TUCSON, AZ 85705) BLDG 2 Commercial New Building Permit
11/01/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/1/2023 11:00:23 AM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/1/2023 10:59:02 AM
Please clearly identify all drawings and details applicable to this permit and specify the drawings and details not under this permit as "under a separate permit - for reference only".

1) General: The electrical panel schedule for building 1 shows circuits for classrooms, bathrooms, and offices that are not included in the other sheets. Clarify and coordinate all rooms in existing building 1 and revise all affected sheets. (2018 IBC section 107)

2) Sheet G100: The lobby of building1 1 is to be calculated at 1 person per 5 sf for standing space only, 1 per 7 sf for seating only, or 1 per 15 for table and chair seating. If there are classrooms, they are not to be calculated as offices. Please revise all affected sheets and plumbing fixture calculations. (2018 IBC section 1004, Table 1004.5)

3) Sheets G100, A100, A400: The toilet facilities do not include the lavatories in the same room. Please revise all sheets. (2018 IBC sections 2902.3, 1109.2.1, 2018 IPC Toilet Facility definition, section 405.3.2)

4) Sheets G100, A100, A400: The doors cannot swing into the required water closet clear floor spaces. Please revise all affected sheets. (2009 ICC A117.1 sections 603.2.2, 604.3)


5) Sheet S0.1 Provide the list of specific special inspections. (2018 IBC Chapter 17)

6) Sheet S3.1 Provide the ramp and guard construction details and dimensions. (2018 IBC sections 1012, 1015, 2009 ICC A117.1 sections 405, 405.8, 405.9)

7) Sheet A100 (Floor Plan): The existing garage or covered parking is not shown. (2018 IBC section 107)

8) Sheet A103 (Roof Plans): Include the roof drainage details. (2018 IPC sections, 1101.1, 1105, 1106, 1108)

9) Sheet A300 (Stair Section): The riser and tread dimensions are not shown. (2018 IBC section 1105)

10) Sheet A400 (Accessibility Details): Show the accessible signage details. (2009 ICC A117.1 section 703)

11) Sheet A601 (Window and Door Schedules): Include the U-Factors of the windows and doors meeting the energy code requirements. (2018 IECC section C402)

12) Sheet P102 (Plumbing Diagrams): Include the plumbing diagrams and calculations for building 1. (2018 IPC section 106.3.1)

13) Sheet E2.0 (Electrical Plans): Show kitchen receptacles as GFCI protected. (2017 NEC section 210.8)

14) Sheet E2.0 (Electrical Plans): Missing the HVAC service GFCI receptacles. (2017 NEC sections 210.8, 210.63)

15) Sheet E4.0 (Electrical Schedule and Diagram): The one-line diagram feeder schedule shows 4 feeder conductors and service conductors are being installed for a single-phase system. Please clarify. (2018 IBC section 107)

16) Sheet E4.0 (Electrical Schedule and Diagram): The one-line diagram shows that the panel for building one is a main lug 17) Sheet E4.0 (Electrical Schedule and Diagram): The panel schedule for building 1 shows circuits for rooms that are not
include in the plans shown on other sheets and there are kitchen, HVAC, and other equipment circuits not included in the schedule and calculations. Please revise and coordinate all affected sheets. (2017 NEC sections 110.22, 210.5)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/1/2023 10:59:49 AM
See the building review comments.




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/1/2023 10:59:33 AM
See the building review comments.



Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 11/1/2023 11:00:04 AM
See the building review comments.
11/14/2023 Fire New Construction REQUIRES RESUBMIT -Exits from courtyard shall lead to a public way. Provide exiting plan from courtyard.
Provide details on side hinged gate, SE side of courtyard. Most probably will need to swing in direction of egress travel and have panic hardware. Occupant load requires two exits from courtyard.
-E portion of building is 1028+1018=2046/20=102 OL. OL>100 requires voice evac alarm per 907.2.3.
john.vincent@tucsonaz.gov
5203495581




-Shared Studio Session 923-111-188 - Master Permit TC-COM-1023-02482 (1131 N 6TH AV TUCSON, AZ 85705)/BLDG 1 Commercial Addition/Alteration Permit AND COVERS IMPROVEMENTS FOR TC-COM-1023-02523 (1131 N 6TH AV TUCSON, AZ 85705) BLDG 2 Commercial New Building Permit
11/22/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
11/07/2023 Site Zoning REQUIRES RESUBMIT -Shared Studio Session 923-111-188 - Master Permit TC-COM-1023-02482 (1131 N 6TH AV TUCSON, AZ 85705)/BLDG 1 Commercial Addition/Alteration Permit AND COVERS IMPROVEMENTS FOR TC-COM-1023-02523 (1131 N 6TH AV TUCSON, AZ 85705) BLDG 2 Commercial New Building Permit


ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1023-02482 & TC-COM-1023-02523
1131 N. 6th Av. – C-2
Charter School (1st Review)

TRANSMITTAL: November 7, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.21), Educational Use: Elementary and Secondary school is a permitted use in the zone. This school is not subject to UDC Requirements based on Zoning Administrator Exemption for Charter Schools letter dated 2022.06.03.

1. Until development package (DP) TD-DEV-1023-00417 is approved by all review agencies Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/26/2023 PDSD Application Completeness Express REVIEW COMPLETED -Shared Studio Session 923-111-188 - Master Permit TC-COM-1023-02482 (1131 N 6TH AV TUCSON, AZ 85705)/BLDG 1 Commercial Addition/Alteration Permit AND COVERS IMPROVEMENTS FOR TC-COM-1023-02523 (1131 N 6TH AV TUCSON, AZ 85705) BLDG 2 Commercial New Building Permit