Permit Number: TC-COM-1023-02441
Parcel: 10821328B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02441
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2023 Site Zoning APPROVED
11/08/2023 Water - PDSD APPROVED
11/06/2023 Site Engineering NOT REQUIRED
11/08/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/30/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/27/2023 11:43:58 AM
See the building review comments.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/27/2023 11:41:35 AM
1) Sheet A1.0 (Cover Sheet): Provide a brief description of the type of business use of the space. (2018 IBC section 107)

2) Sheet A1.0 (Cover Sheet): The reception/waiting room and the break room are areas of assembly and are to be calculated at 1 person per 15sf, 7sf, or 1/5sf. Please revise affected details. (2018 IBC Table 1004.5)

3) Sheets A1.0 and 1.1: The area and occupancy calculations on sheet A1.1 do not match the details shown on other sheets. Please coordinate all sheets. (2018 IBC section 107)

4) Sheet A2.0: Include the accessibility details. (2009 ICC A117.1)

5) Sheet E1.0 (Power Plan): Show GFCI protected receptacles in the break room. (2017 NEC 210.8)

6) Sheet E1.0 (Power Plan): Specify tamper-resistant receptacles required by 2017 NEC section 406.12.

7) Sheet E1.0 (Power Plan): Include the one-line diagram (new and existing equipment), panel schedule, load calculations, grounding, etc. (2018 IBC section 107)

8) Sheet E2.0 (Lighting Plan): Show the energy code compliance calculations or COMcheck. Include the lighting specifications. (2018 IECC section C405)



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/27/2023 11:43:26 AM
See the building review comments.



Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/27/2023 11:43:11 AM
See the building review comments.




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/27/2023 11:43:42 AM
See the building review comments.
11/08/2023 Fire New Construction REVIEW COMPLETED
10/19/2023 PDSD Application Completeness REVIEW COMPLETED