Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/24/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. The registrant seal is not valid without the Discipline or Branch in which the Engineer is registered as included in the seal. Ref; State of Arizona Board of Technical Registration R4-30-303 (A).

2. Indicate the branch circuit and panel designation for each device on the electrical floor plans and correlate with the panel schedule(s). NEC 408.4.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC.
10/26/2023 Commercial Plumbing REQUIRES RESUBMIT 1. If the proposed reverse osmosis system does not have a listed, integral backflow preventer or integral air gap conforming to Section 608.14.1, IPC 2018, provide backflow prevention. Specify the type of backflow prevention device required for the domestic water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
2. The water connection to each misting system shall be individually protected against backflow and cross-contamination. Specify the device to be used for the water connection. Reference: Sections 608.1 and 608.17.6, IPC 2018.
10/16/2023 PDSD Application Completeness REVIEW COMPLETED