Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1023-02416
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/14/2023 | Commercial Electrical | REQUIRES RESUBMIT | No compliance with the previous plan review comment. See State of Arizona Board of Technical Registration R4-30-303(A), R4-30-304(E)(4). | ||
11/08/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Comment not addressed. [Initial comment: If the proposed reverse osmosis system does not have a listed, integral backflow preventer or integral air gap conforming to Section 608.14.1, IPC 2018, provide backflow prevention. Specify the type of backflow prevention device required for the domestic water connection. Reference: Sections 608.1 and 608.3, IPC 2018.] 2. Comment not addressed. [Initial comment: The water connection to each misting system shall be individually protected against backflow and cross-contamination. Specify the device to be used for the water connection. Reference: Sections 608.1 and 608.17.6, IPC 2018.] 3. Provide a written response to each of the comments. |
||
11/03/2023 | PDSD Application Completeness | REVIEW COMPLETED |