Permit Number: TC-COM-1023-02375
Parcel: 14041124E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1023-02375
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2024 Site Zoning APPROVED
03/28/2024 Water - PDSD APPROVED
03/18/2024 Site Engineering NOT REQUIRED
03/28/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/11/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 3/5/2024 2:49:11 PM



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 3/4/2024 2:21:44 PM
1. General: Include the drawings and specifications for the compactor, and the auger. (2018 IBC section 107)

2. Sheet G0.2: Provide the scope of work, description of the items stored and processes taking place in the different areas. Label the uses of all spaces and equipment. (2018 IBC section 107)


Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/6/2024 4:08:17 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 3/6/2024 10:22:29 AM
Electrical Review of SSD-SAZ3
By: Ron Ross PE
E1.3A MECHANICAL POWER PLAN AREA A: Need to provide circuit information for equipment receptacles. Outdoor receptacles need to be weather proof GFCI protected as per NEC 210.63.

E1.3B MECHANICAL POWER PLAN AREA B: Need to provide circuit information for equipment receptacles. Outdoor receptacles need to be weather proof GFCI protected as per NEC 210.63.

E1.3C MECHANICAL POWER PLAN AREA C: Need to provide circuit information for equipment receptacles. Outdoor receptacles need to be weather proof GFCI protected as per NEC 210.63.

E1.3D MECHANICAL POWER PLAN AREA D: Need to provide circuit information for equipment receptacles. Outdoor receptacles need to be weather proof GFCI protected as per NEC 210.63.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/9/2024 8:45:29 AM
Plumbing Revisions: Ok
03/25/2024 Fire New Construction REVIEW COMPLETED
03/01/2024 PDSD Application Completeness REVIEW COMPLETED