Permit Number: TC-COM-0926-01543
Parcel: 14041134D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0926-01543
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2026 Commercial Building APPROVED
09/24/2026 Commercial Electrical APPROVED
10/05/2026 Site Zoning APPROVED
10/05/2026 Commercial Plumbing NOT REQUIRED
09/21/2026 Site Engineering NOT REQUIRED
10/05/2026 Water - PDSD NOT REQUIRED
10/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/05/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01543
ADDRESS/PARCEL: 6803 S PALO VERDE RD TUCSON, AZ 85756

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please clarify why the 574 sq. ft. office area is classified as a conference/meeting space with 30 occupants in the outdoor air calculations when it is shown as an office with 5 occupants on Sheet A0.6. Please also ensure the areas listed in the outdoor air calculations are consistent with the square footages shown on Sheet A0.6. Reference: Section 107.2.1, IBC 2024.
2. Please provide heating and cooling load calculations to justify the heating/cooling capacity of the new package heat pump. Reference: Section C403.1.1 and C502.3.3, IECC 2024.
10/05/2026 Fire New Construction REVIEW COMPLETED
09/21/2026 PDSD Application Completeness Express REVIEW COMPLETED