Permit Number: TC-COM-0926-01520
Parcel: 11504492A

Address:
901 E 1ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0926-01520
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/14/2026 Commercial Mechanical Express REQUIRES RESUBMIT 1. Provide the specifications for the replacement HVAC unit (e.g., heating/cooling capacity, and efficiency ratings).
2. Verify that the unit will comply with Sections C403.2.2, C403.3.2, C403.4 and C403.5, IECC 2024 for efficiency, controls, and economizer.
3. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed . Reference: Section C403.3.1, IECC 2024.
4. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.3, IECC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/10/2026 PDSD Application Completeness Express REVIEW COMPLETED