Permit Number: TC-COM-0926-01421
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0926-01421
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2026 Commercial Electrical Standard APPROVED
09/29/2026 Commercial Mechanical Standard APPROVED
09/29/2026 Commercial Plumbing Standard APPROVED
09/28/2026 Site Zoning Standard APPROVED
09/29/2026 Water - PDSD Standard APPROVED
09/16/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
09/14/2026 Site Engineering Standard NOT REQUIRED
09/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.

Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. The building appears to be classified as a Risk Category IV structure. Verify the Risk Category and provide the required special inspection for through-penetration firestops, membrane-penetration firestops, and fire-resistant joint systems in accordance with 2024 IBC Section 1705.18.
Please provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

2. Please amend the plans to show that all through-penetrations and membrane penetrations of fire-resistance-rated assemblies are protected with approved firestopping systems. Provide detail drawings on the plans identifying the specific UL-listed (or equivalent) firestopping systems for pipe, conduit, and duct penetrations through rated walls, floors, and ceilings (e.g., putty pads, firestop sealants, collars, or sleeves, as applicable). Per 2024 IBC Section 714.1 through714.4.3 & 714.5.4

3. For each fire-resistance-rated wall assembly shown on the construction drawings, please provide the corresponding listed assembly detail (cut sheet) on the plans. The detail shall include, at a minimum:

The listing designation (e.g., UL, GA, Intertek/WHX, or other approved listing).
A drawing or cross-section of the assembly showing the required construction.
A list of all required components, including framing, gypsum board, insulation, fasteners, joint treatment, and any other materials required by the tested assembly.
The required hourly fire-resistance rating.
Any applicable limitations, continuity requirements, and installation requirements necessary to maintain the fire-resistance rating.

This information is necessary because many tested fire-resistance-rated assemblies require specific proprietary materials and installation methods that cannot be verified from a generic wall section alone. Substituting materials or omitting required components may invalidate the fire-resistance rating of the assembly.

Providing the listed assembly details on the drawings allows the design team, contractor, inspectors, and plan reviewers to verify that each fire-resistance-rated wall is constructed in accordance with its tested and approved assembly. 2024 IBC Sections 703.2, 703.3, and 107.2.1.
4. Sheet G-014: Please update the Accessibility Code reference to indicate the 2017 ICC A117.1 edition


Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/30/2026 Fire New Construction Standard REQUIRES RESUBMIT -Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
09/08/2026 PDSD Application Completeness Express REVIEW COMPLETED