Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0925-01782
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2025 | Water - PDSD Standard | APPROVED | |||
| 10/13/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 10/29/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/21/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please provide the fire-resistance rating of all walls and elements adjoining space on the floor’s plan view. IBC 602.1 2. Please identify the fire walls, fire barriers, fire partitions, smoke barriers, and smoke partitions are labeled with their name, as used in the IBC. IBC 107.2.1, 911.1.6 item 13 3. Please show how the separated occupancies are separated with fire barriers and horizontal assemblies with the required fire-resistance rating from Table 508.4. IBC 508.4.4 4. Please show the following means of egress information for the proposed future tenant spaces. A. The total number of occupants for the story or floor is shown. IBC 107.2.3 B. The number of occupants is shown for every room and space. IBC 107.2.3 C. The occupant load factor and area are shown for every room and space. IBC 1004.5 D. The occupant load factor used reflects the use/function of the space. IBC 1004.5 E. The number of occupants being served by each egress door and stairway is shown. IBC 107.2.3 F. The size of each egress door and stairway is shown and is compared to allowable. IBC 1005.3 • Exception 1 reduced widths are only allowed if an emergency voice/alarm is provided. G. The loss of one means of egress does not reduce required capacity by more than 50%. IBC 1005.5 5. Please provide the following path of egress information. A. The paths of egress are shown. IBC 107.2.3 B. The exit access travel distance is dimensioned with a clear start and stop point. IBC 1017.2 C. The common path of egress travel is dimensioned with a clear start and stop point. IBC 1006.2.1 D. Two paths of egress are provided from spaces and stories that require it. IBC 1006.2.1, 1006.3 E. Exits and exit access components are separated by 1/3rd the distance of the space. IBC 1007.1 6. Please provide the agency listing report number, or evaluation report for the EFIS system to be used IBC 107.2.1 Additionally, please provide the water resistance barrier evaluation report as well. For example, ICC-ES ERS-1232 Evaluation Report Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 10/13/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0925-01782 (5950 E BROADWAY BL Unit:UNIT 150 TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide electrical load calculations, for the Main Service Panel, and each new distribution panel, Per NEC 220.40. 2. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24. 3. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/21/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. | ||
| 10/21/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Coordinate the keynotes on P2.0 with the keynote entries on the Plumbing Plan – Roof Level on P2.0 (e.g., #2, new medium pressure gas connects to #8, existing CW pipe above ceiling and then terminates as #4, low pressure gas up to roof). Reference: Section 107.2.1, IBC 2018. 2. Provide sizing calculations for the gravity grease interceptors based upon Section 1003.3, IPC 2018, as amended by the City of Tucson, not Section 1003.3.5, IPC 2021. A 1500-gallon gravity grease interceptor does not have capacity for 172 DFU’s. |
||
| 10/14/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0925-01782 Location: 5950 E BROADWAY BL Unit: UNIT 150 Review Date: 10/14/2025 Site Engineering Comments: 1. As the proposed project is an expansion of the site a development package is required, UDC Article 3.3.3.G.2.c A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. 2. Site Engineering will be unable to review and approve permit TC-COM-0925-01782 until the associated development package TD-DEV-0325-00090 is reviewed and approved by all reviewers. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 10/29/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0925-01782 - TD-DEV-0325-00090 5950 E BROADWAY BL. - C-2 Food Service (1st Review) TRANSMITTAL DATE: October 29, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Food Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P. 1. Comment: Zoning has reviewed the commercial building plans for compliance with Development Package (DP) TD-DEV-0325-00090 and all though the plans appear to match until the DP is approved by all review agencies Zoning cannot approve this permit. If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov. |
||
| 10/17/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 09/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |