Permit Number: TC-COM-0925-01779
Parcel: 141186020

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01779
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 10/11/2025 4:53:00 PM
10/14/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/13/2025 4:31:03 PM
Shell permit only. All tenant space buildout will require additional plan review and permits.
10/17/2025 Water - PDSD Standard APPROVED
10/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/14/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/13/2025 10:40:47 AM
1. GENERAL/GEOTECHNICAL REPORT: Please provide a copy of the site-specific geotechnical report for this project.
The report should support the appropriateness of the selected foundation system for the project site. [All submitted
geotechnical reports must be dated no later than three years from the submittal date. - AREA SPECIFIC] Outdated
reports must be accompanied by a letter from a qualified geotechnical engineer stating that the report requirements
are still valid, or stating what items may have changed. All building code references must be updated to the current
code adopted by the City of Tucson.
2. GENERAL/STRUCTURAL CALCULATIONS: No structural calculations have been provided. Please provide the
structural calculations for this project.




Building(B) Reviewer
Andrew Frame
aframe@safebuilt.com
Denied
Reason:
Date Completed : 10/13/2025 3:03:57 PM
10/13/2025 Review Requires Resubmittal AFrame:
1) Please provide a completed Building COMcheck and resubmit for review.
2) Sheet A2.1, and A2.2-Wall Detail D: Wall Detail D referenced UL 305. Please provide full /complete UL U305 details on
plan set and resubmit plan set for review.
10/14/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/4/2025 11:30:56 PM
First Plumbing Review:
1), Plan Page A4.0: Missing scupper & Downspouts sizing calculations, Add scupper & Downspouts sizing calculations. -
2018 IPC 1106.3, 1106.5, 1108
10/10/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0925-01779 (10000 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
2. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/08/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0925-01779
Location: 10000 E OLD VAIL RD
Review Date: 10/8/2025
Site Engineering Comments:
1. It appears the downspout and sidewalk scuppers shown on both the roof plan sheet 7 and sheet 9 do not match with what was approved through development package TD-DEV-0725-00181. You will find that the DP provides keynotes 42 & 43 on sheet 5 delineated on the West side of the structure rather than the east. This will require either a revision to the development package or a revision to the building plans. Revise accordingly.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/23/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0925-01779 - TD-DEV-0725-00181
10000 E OLD VAIL RD – I-1
Shell Building (1st Review)

TRANSMITTAL DATE: October 23, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. Comment: Zoning has reviewed the building plans for compliance with related Development Package (DP) TD-DEV-0725-00181.

2. Comment: The following zoning information is inconsistent between the Building Plans and the Development Plan (DP). Please correct all listed zoning information so that the Building Plans match the DP:

The listed building area does not match what is listed in the DP.

3. Additional comments may be forthcoming based on the proposed use.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Ramiro.Olivarez@tucsonaz.gov.
10/16/2025 Fire New Construction Standard REVIEW COMPLETED
09/29/2025 PDSD Application Completeness Express REVIEW COMPLETED