Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0925-01774
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/01/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | Replacement of an AC unit will require a heating/cooling load calculation to justify the capacity of the unit being installed (Sections R403.7, IECC 2018). The unit itself will also have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency and controls. | ||
| 10/01/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |